Siemens SG035 owner manual Generator Control Operation, Operating Unit with Manual Transfer Switch

Page 15

Standby Generator Sets

Operation

GENERATOR CONTROL AND

OPERATION

Refer to the appropriate control panel operator’s manual for this unit.

OPERATING UNIT WITH MANUAL TRANSFER SWITCH

If the generator was installed in conjunction with a transfer switch capable of manual operation only, the following procedure applies. A manually operated transfer switch is one that will not provide automatic start-up and does not include an intelligence circuit.

‹ENGINE START-UP AND TRANSFER

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

DANGER

The Maintenance Disconnect Switch and the AUTO/OFF/MANUAL switches (if so equipped) must be set properly, or the generator will crank and start as soon as the utility power to the transfer switch is turned off. Refer to applicable control panel and transfer switch manuals for more information.

Do not proceed until certain that utility source voltage is available to the transfer switch and the transfer switch main contacts are set to

UTILITY.

Do not attempt manual operation until all power supplies to the transfer switch have been posi- tively turned off, or extremely dangerous - pos- sibly lethal - electrical shock will result.

Transfer switch enclosure doors should be kept closed and locked. Only authorized personnel should be allowed access to the transfer switch interior. Extremely high and dangerous voltages are present in the transfer switch.

In order to transfer load from the utility source to the generator, follow these directions:

Turn OFF or disconnect the utility power circuit to the transfer switch, using the means provided (such as the utility source main line circuit break- er).

Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to the utility power supply.

Set the standby generator’s main line circuit break- er to its OFF (or OPEN) position.

Start the generator.

Do not crank the engine continuously for longer than 30 seconds, or the heat may

damage the starter motor.

Let engine stabilize and warm up.

Check all applicable instrument and gauge read- ings. When certain that all readings are correct, move the transfer switch manual handle to its STANDBY (GENERATOR) position, i.e., load cir- cuits supplied by the generator.

Set the standby generator’s main line circuit break- er to its ON (or CLOSED) position.

Load circuits are now powered by the standby generator.

‹RETRANSFER AND SHUTDOWN

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

To transfer the load back to the utility power source and shut down the generator, follow these direc- tions:

Set the standby generator’s main line circuit break- er to its OFF (or OPEN) position.

Manually move the transfer switch handle to its UTILITY (NORMAL) position, i.e., load circuits connected to the utility.

Turn ON the utility power supply to the transfer switch, using the means provided (such as the util- ity power source main line circuit breaker).

Let the generator run at no-load for a few minutes to stabilize internal temperatures.

Shut down the generator.

OPERATING UNIT WITH AUTOMATIC TRANSFER SWITCH

If the generator has been installed with an automatic transfer switch, such as an RTS, HTS, or GTS-type transfer switch, the engine may be started and stopped automatically or manually.

NOTE:

Refer to the applicable manual for your trans- fer switch and to “Transfer Switch Start Signal Connections”. In addition, please note the dangers under “Engine Start-up and Transfer.”

9-1

08/05

0 .Rev Oper001

Image 15
Contents SG035 Series 2.4L 35kW Standby Generator Sets Table of Contents  Warning   Electrical Hazards  Introduction ‹ Operation and Maintenance‹ HOW to Obtain Service Authorized Service Dealer Location‹ Data Label Identification RecordEquipment Description Engine OIL RecommendationsCoolant Recommendations Engine Protective Devices ‹ LP Fuel System Fuel System‹ Fuel Requirements ‹ Natural GAS Fuel SystemSpecifications ‹ Cold Weather KIT ‹ Reconfiguring the Fuel SystemGenerator AC Lead Connections Alternator Power Winding Connections‹ FOUR-LEAD, SINGLE-PHASE Stator ‹ 3-PHASE AlternatorsInstallation Preparation Before START-UPInitial Inspection for Genset Startup ‹ Preparation for START-UP START-UP Checklist‹ Retransfer and Shutdown Operating Unit with Manual Transfer SwitchGenerator Control Operation ‹ Engine START-UP and TransferMaintenance Performed by Service Facilities Cooling SystemChecking Fluid Levels Maintenance Owner Operator can Perform ‹ Changing the Engine AIR Cleaner ‹ Coolant Change ‹ Changing Engine OIL‹ Spark Plugs ‹ Battery Maintenance Miscellaneous Maintenance‹ Cleaning the Generator ‹ BatteryKW 150 KW Standby GAS Engine Driven Generator Sets Service ScheduleMaintenance Level 11-3 11-4 Problem Cause Correction Troubleshooting GuideStandby Generator Sets Standby Generator Sets Standby Generator Sets Page PAN CB Conn BOX Page UL Circuit Breaker QJ-2P Page Instr Hypot Test not Shown Page Components Included in 0G1290E Page Weldment Frame 2.4L C2 Page Battery Tray C1 CPL Page Gasket Bosch 32 Page Engine 2.4L G2 Rework Page Weldment Radiator Support 2.4L Page Flange Fuel Inlet Page Bracket Muffler Page Rear Wrap C2 CPL Page Page Page Page Page Page Page Page Page Page Page C2 Units Standby Generator Sets Warranty

SG035 specifications

The Siemens SG035 is a versatile and innovative solution designed for the modern industrial landscape. As a significant model within Siemens’ range of power generation equipment, the SG035 delivers reliable performance, advanced technology, and a commitment to sustainability. This article explores the main features, technologies, and characteristics that set the Siemens SG035 apart from its competitors.

One of the primary features of the Siemens SG035 is its impressive power output. It is engineered to provide a substantial amount of energy, making it ideal for a wide range of applications, from industrial to commercial settings. The unit is equipped with a state-of-the-art generator that ensures maximum efficiency and minimal energy losses.

The SG035 incorporates cutting-edge technology that enhances its operational capabilities. For instance, it utilizes advanced control systems that allow for real-time monitoring and adjustments, ensuring optimal performance under varying load conditions. These control systems are designed with user-friendly interfaces, making it easier for operators to manage the equipment.

In terms of design, the Siemens SG035 boasts a compact and modular architecture. This allows for easy integration into existing energy systems, saving valuable space on facilities. Furthermore, its modular design facilitates rapid installation and maintenance, reducing downtime and operational costs.

Another significant characteristic of the SG035 is its focus on sustainability. It has been engineered to meet stringent environmental standards, including low emissions and high energy efficiency. The use of environmentally friendly materials in its construction further underscores Siemens’ commitment to sustainable practices.

The Siemens SG035 also prioritizes safety and reliability. It is built with robust components designed to withstand harsh operating conditions. Additionally, extensive safety features are integrated into the system to protect both the equipment and the personnel operating it.

Overall, the Siemens SG035 stands out in the field of power generation equipment due to its powerful performance, advanced technologies, compact design, and commitment to environmental sustainability. As industries continue to evolve and require more efficient energy solutions, the Siemens SG035 positions itself as a reliable choice for meeting contemporary energy demands while prioritizing safety, efficiency, and the environment. This makes it a significant player in the move towards a more sustainable future in energy production.