TECHNICAL SPECIFICATION
❥✱Floor/Ceiling YOHC (YOKC-YOJC)R-410A 50Hz Rev.291106
| | Set | | YOHC12FSA(B)AAR | YOHC18FSA(B)AAR | YOHC24FSA(B)AAR | YOHC30FSA(B)ACR | YOHC30FSA(B)AAR | YOHC36FSA(B)AAR | YOHC36FSA(B)ACR | YOHC48FSA(B)ACR | YOHC60FSA(B)ACR |
| Model | Indoor unit | | YOKC12FS-A(B)AR | YOKC18FS-A(B)AR | YOKC24FS-A(B)AR | YOKC30FS-A(B)CR | YOKC30FS-A(B)AR | YOKC36FS-A(B)AR | YOKC36FS-A(B)CR | YOKC48FS-A(B)CR | YOKC60FS-A(B)CR |
| Power supply | Outdoor Unit | Ph-V-Hz | YOJC12FS-A(B)AR | YOJC18FS-A(B)AR | YOJC24FS-A(B)AR | YOJC30FS-A(B)CR | YOJC30FS-A(B)AR | YOJC36FS-A(B)AR | YOJC36FS-A(B)CR | YOJC48FS-A(B)CR | YOJC60FS-A(B)CR |
| | 1,220-240V, 50Hz | 1,220-240V, 50Hz | 1,220-240V, 50Hz | 3,380V, 50Hz | 1,220-240V, 50Hz | 1,220-240V, 50Hz | 3,380V, 50Hz | 3,380V, 50Hz | 3,380V, 50Hz |
| | | Btu/h | 12,000 | 18,000 | 24,000 | 30,000 | 30,000 | 36,000 | 36,000 | 48,000 | 60,000 |
| | Capacity | kW | 3.5 | 5.4 | 7.1 | 9.2 | 9.2 | 10.5 | 10.5 | 14 | 17 |
| Cooling | | kcal/h | 3,024 | 4,536 | 6,048 | 7,560 | 7,560 | 9,072 | 9,072 | 12,096 | 15,120 |
| | Input | W | 1,200 | 1,900 | 2,700 | 3,750 | 3,750 | 3,750 | 3,750 | 4,700 | 6,000 |
| | Rated current | A | 6 | 8.5 | 12 | 6.3 | 16.3 | 16.3 | 6.6 | 8.2 | 9.8 |
| | | Btu/h | 13,000 | 20,500 | 27,300 | 32,000 | 32,000 | 39,000 | 39,000 | 52,000 | 68,000 |
| | Capacity | kW | 3.8 | 6 | 8 | 9.4 | 9.4 | 11.4 | 11.4 | 15.2 | 20 |
| Heating | | kcal/h | 3,276 | 5,166 | 6,880 | 8,064 | 8,064 | 9,828 | 9,828 | 13,104 | 17,136 |
| | Input | W | 1,130 | 1,850 | 2,800 | 3,500 | 3,500 | 3,500 | 3,700 | 4,900 | 6,000 |
| | Rated current | A | 5 | 8 | 12.5 | 5.2 | 15.2 | 15.2 | 6.5 | 8.6 | 9.8 |
| Moisture Removal | | L/h | 1.2 | 1.8 | 2.4 | 3 | 3 | 3.6 | 3.8 | 4.8 | 6 |
| Max. input consumption | W | 1,500 | 2,400 | 3,300 | 4,620 | 4,620 | 4,620 | 4,400 | 5,870 | 7,500 |
| Max. current | | A | 7 | 11.5 | 14.5 | 7.1 | 21 | 21 | 8 | 10.7 | 12.8 |
| Starting current | Type | A | 26 | 36.8 | 61 | 61 | 97 | 97 | 61 | 66 | 67 |
| | | ROTARY | ROTARY | ROTARY | SCROLL | SCROLL | SCROLL | SCROLL | SCROLL | SCROLL |
| | Input | W | 1,145 | 1,870 | 2,430 | 3,650 | 3,650 | 3,650 | 3,650 | 4,750 | 5,750 |
| Compressor | Rated current (RLA) | A | 5.3 | 8.75 | 11.4 | 6.58 | 17.65 | 17.65 | 6.58 | 8.22 | 9.77 |
| Locked rotor Amp (LRA) | A | 26 | 36.8 | 61 | 61 | 97 | 97 | 61 | 66 | 67 |
| |
| | Thermal protector | | Inner | Inner | Inner | Inner | Inner | Inner | Inner | Inner | Inner |
| | Capacitor | μF | 35/370μF/V | 50/370μF/V | 50/400μF/V | / | 60μF/440V | 60μF/440V | / | / | / |
| | Input | W | 104/98 | 110/104/98 | 110/104/98 | 142/134/132 | 142/134/132 | 142/134/132 | 142/134/132 | 118/108/101 | 118/108/101 |
| Indoor fan motor | Capacitor | μF | 1.5μF/450V | 2.5μF/450V | 2.5μF/450V | 3.5μF/450V | 3.5μF/450V | 3.5μF/450V | 3.5μF/450V | 2.5μF/450V | 2.5μF/450V |
| | Speed (Hi/Med/Low) | r/min | 1,190/1,000/890 | 1,280/1,190/1,000 | 1,280/1,190/1,000 | 1,310/1,200/1,000 | 1,310/1,200/1,000 | 1,310/1,200/1,000 | 1,310/1,200/1,000 | 820/695/620 | 820/695/620 |
| | Number of rows | | 2 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 |
| | Tube pitch(a) row pitch(b) | mm | 25.422 | 25.422 | 25.422 | 25.422 | 25.422 | 25.422 | 25.422 | 25.422 | 25.422 |
| Indoor coil | Fin spacing | mm | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 |
| Fin type | | | | | | Hydrophilic aluminum | | | | |
| | | | | | | | | | |
| | Tube outside dia. and type | mm | | | | | Ø9.53 innergroove tube | | | | |
| | Coil length height width | mm | 80425444 | 80425466 | 80425466 | 90520366 | 90520366 | 90520366 | 90520366 | 1,15025466 | 1,15025466 |
| Indoor air flow (Hi/Mid/Low) | m3/h | 600/480/400 | 800/600/500 | 1,000/900/700 | 1,200/1,000/800 | 1,400/1,200/1,000 | 1,400/1,200/1,000 | 1,400/1,200/1,000 | 2,000/1,800/1,600 | 2,000/1,800/1,600 |
| Indoor noise level (Hi/Mid/Lo) | dB(A) | 43/41/38 | 43/41/38 | 45/43/40 | 45/43/40 | 45/43/40 | 45/43/40 | 45/43/40 | 47/45/42 | 47/45/42 |
| | Dimension (W*H*D) | mm | 995660198 | 995660198 | 995660198 | 1,285660198 | 1,285660198 | 1,285660198 | 1,285660198 | 1,670680240 | 1,670680240 |
| Indoor unit | Packing (W*H*D) | mm | 1,075744278 | 1,075744278 | 1,075744278 | 1,365744278 | 1,365744278 | 1,365744278 | 1,365744278 | 1,764760329 | 1,764760329 |
| | Net/Gross weight | kg | 29/35 | 30/37 | 30/37 | 34/42 | 34/42 | 34/42 | 34/42 | 52/62 | 52/62 |
| Outdoor fan | Input | W | 56 | 130 | 130 | 307 | 307 | 307 | 307 | 138+156 | 138+156 |
| Capacitor | μF | 2.5μF/450V | 2.5μF/450V | 3μF/450V | 10μF/450V | 10μF/450V | 10μF/450V | 10μF/450V | 3.52μF/450V | 3.52μF/450V |
| motor |
| Speed | r/min | 800 | 750 | 800 | 740 | 740 | 740 | 740 | 800 | 800 |
| | Number of rows | | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
| | Tube pitch(a) row pitch(b) | mm | 25.422 | 25.422 | 25.422 | 25.422 | 25.422 | 25.422 | 25.422 | 25.422 | 25.422 |
| | Fin spacing | mm | 1.4 | 1.7 | 1.5 | 1.7 | 1.7 | 1.7 | 1.7 | 1.8 | 1.8 |
| Outdoor coil | Fin type | | | Hydrophilic aluminum | | | Unhydrophilic aluminium | | Hydrophilic aluminum |
| | Tube outside dia. and type | mm | | | | | Ø9.53x0.35,Innergroove tube | | | | |
| | Coil length height width | mm | 65155944 | 77566044 | 85081044 | 95591544 | 95591544 | 95591544 | 95591544 | 715122044 | 715122044 |
| Outdoor air flow | Number of circuits | m3/h | 2 | 3 | 4 | 8 | 8 | 8 | 8 | 4 | 4 |
| | 2,100 | 2,400 | 3,000 | 5,000 | 5,000 | 5,000 | 5,000 | 6,000 | 6,000 |
| Outdoor noise level | | dB(A) | 43 | 48 | 55 | 57 | 57 | 57 | 57 | 58 | 58 |
| | Dimension (W*H*D) | mm | 760590285 | 845695335 | 895860330 | 990960360 | 990960360 | 990960360 | 990960360 | 9401,245340 | 9401,245340 |
| Outdoor unit | Packing (W*H*D) | mm | 887655355 | 970770395 | 1,043915395 | 1,1201,090435 | 1,1201,090435 | 1,1201,090435 | 1,1201,090435 | 1,0581,380435 | 1,0581,380435 |
| | Net/Gross weight | kg | 44/48 | 57/62 | 68/70 | 90/102 | 90/102 | 90/102 | 90/102 | 112/127 | 112/127 |
| Refrigerant type/Quantity | g | R-410A/1,120 | R-410A/2,050 | R-410A/2,600 | R-410A/3,100 | R-410A/3,450 | R-410A/3,450 | R-410A/3,100 | R-410A/4,000 | R-410A/4,200 |
| Design pressure (high side/low side) | MPa | 4.2/2.5 | 4.2/2.5 | 4.2/2.5 | 4.2/2.5 | 4.2/2.5 | 4.2/2.5 | 4.2/2.5 | 4.2/2.5 | 4.2/2.5 |
| Refrigerant | Liquid side | mm (inch) | 6.35 (1/4) | 6.35 (1/4) | 9.53 (3/8) | 12.7 (1/2) | 12.7 (1/2) | 12.7 (1/2) | 12.7 (1/2) | 12.7 (1/2) | 12.7 (1/2) |
| Gas side | mm (inch) | 12.7 (1/2) | 12.7 (1/2) | 16 (5/8) | 19 (3/4) | 19 (3/4) | 19 (3/4) | 19 (3/4) | 19 (3/4) | 19 (3/4) |
| piping | Max. pipe length | m | 25 | 25 | 30 | 30 | 30 | 30 | 30 | 50 | 50 |
| | Max. difference in level | m | 15 | 15 | 15 | 20 | 20 | 20 | 20 | 30 | 30 |
| Operation temp | | ºC | 17~30 | 17~30 | 17~30 | 17~30 | 17~30 | 17~30 | 17~30 | 17~30 | 17~30 |
| Ambient temp | | ºC | -7~45 | -7~45 | -7~45 | -7~45 | -7~45 | -7~45 | -7~45 | -7~45 | -7~45 |
| Qty’per 20’& 40’Fcl | | Pieces | 63/138/155 | 49/104/126 | 44/94/101 | 27/55/62 | 27/55/62 | 27/55/62 | 27/55/62 | 25/50/54 | 25/50/54 |
❥✱Floor/Ceiling DC Inverter “YOHC” R-410A, 50Hz
| | Set | | YOHC18DSBAAR | YOHC24DSBAAR | YOHC36DSBACR | YOHC48DSBACR | YOHC60DSBACR |
| Model | Indoor | | YOKC18DS-BAR | YOKC24DS-BAR | YOKC36DS-BCR | YOKC48DS-BCR | YOKC60DS-BCR |
| | Outdoor | | YOJC18DS-BAR | YOJC24DS-BAR | YOJC36DS-BCR | YOJC48DS-BCR | YOJC60DS-BCR |
| Power supply | | V-Ph-Hz | 220~240-1-50 | 220~240-1-50 | 380V~3~ 50Hz | 380V~3~ 50Hz | 380V~3~ 50Hz |
| | Capacity | Btu/h | 18,000 | 24,000 | 36,000 | 48,000 | 60,000 |
| Cooling | Input | W | 1,550 | 2,220 | 3,290 | 4,300 | 4,940 |
| | Rated current | A | 6.8 | 9.25 | 8.77 | 11.47 | 11.47 |
| | Capacity | Btu/h | 21,000 | 28,000 | 40,000 | 53,000 | 62,000 |
| Heating | Input | W | 1,680 | 2,250 | 3,160 | 4,170 | 4,880 |
| | Rated current | A | 7.35 | 9.4 | 8.33 | 10.99 | 11.4 |
| Max. input consumption | W | 2,500 | 2,750 | 3,880 | 4,850 | 5,990 |
| Max. current | | A | 10 | 11 | 10.17 | 12.98 | 15.69 |
| Starting current | Type | A | 1.08 | 1.15 | 1.1 | 1.16 | 1.23 |
| | | | DC Inverter Rotary | | DC Inverter Scroll | |
| | Input | W | 1,650 | 1,650 | 3,665 | 3,665 | 3,665 |
| | Rated current (RLA) | A | 8 | 8 | 7.8 | 7.8 | 7.8 |
| Compressor | Locked rotor Amp (LRA) | A | 28 | 28 | 28 | 28 | 28 |
| | Protector | | | | Thermal | | |
| | Capacitor | μF | 50 | 50 | 50 | 50 | 50 |
| | Refrigerant oil | ml | 480 | 480 | 500 | 500 | 500 |
| | Type | | | | AC Motor | | |
| Indoor fan motor | Input | W | 110 | 110 | 134 | 89.5 | 59 |
| Capacitor | μF | 2.5 | 2.5 | 3.5 | 2.5 | 2.5 |
| |
| | Speed (Hi/Me/Lo) | r/min | 1,310/1,190/1,020 | 1,310/1,190/1,020 | 1,265/1,165/1,075 | 1,170/1,070/995 | 1,145*1,035*975 |
| | Number of rows | | 3 | 3 | 3 | 3 | 3 |
| | Fin spacing | mm | 1.8 | 1.8 | 1.8 | 1.8 | 1.8 |
| Indoor coil | Fin type | | | | Hydrophilic aluminium | | |
| Tube outside dia. | mm | | | Ø9.52 | | |
| | | | | |
| | Tube Material | | | | Innergroove tube | | |
| | Coil length height width | mm | 82825466 | 82825466 | 90520366 | 115025466 | 115025466 |
| Indoor air flow (Hi/Me/Lo) | m3/h | 910/810/700 | 910/810/700 | 1,400/1,200/1,000 | 2,000/1,800/1,600 | 2,000/1,800/1,600 |
| Indoor noise level (Hi/Me/Lo) | dB(A) | 49.5/-/- | 53/-/- | 45/43/40 | 47/45/42 | 47/45/42 |
| | Dimension (W*H*D) | mm | 980660195 | 980660195 | 1,285660198 | 1,670680240 | 1,670680240 |
| Indoor unit | Packing (W*H*D) | mm | 1,089744296 | 1,089744296 | 1,379744296 | 1,764760329 | 1,764760329 |
| | Net/Gross weight | kg | 29/35 | 29/35 | 37/42 | 54/61 | 54/61 |
| | Input | W | 129 | 150 | 307 | 150*2 | 150*2 |
| Outdoor fan motor | Capacitor | μF | 3 | 3 | 10 | 3.5*2 | 3.5*2 |
| | Speed | r/min | 770 | 800 | 740 | 800 | 800 |
| | Number of rows | | 2 | 2 | 1 | 1 | 1 |
| | Fin spacing | mm | 1.7 | 1.5 | 1.7 | 1.8 | 1.8 |
| | Fin type | | | | Hydrophilic aluminium | | |
| Outdoor coil | Tube outside dia. | mm | | | Ø9.52 | | |
| | Tube Material | | | | Innergroove tube | | |
| | Coil length height width | mm | 63066044 | 62081344 | 95591522 | 71561022 | 1,15030566 |
| Outdoor air flow | Number of circuits | m3/h | 4 | 2 | 8 | 4 | 4 |
| | 2,400 | 3,000 | 5,000 | 6,000 | 6,000 |
| Outdoor noise level | | dB(A) | 56 | 55 | 57 | 58 | 58 |
| | Dimension (W*H*D) | mm | 840677310 | 894860302 | 990960340 | 9401,245340 | 9401,245340 |
| Outdoor unit | Packing (W*H*D) | mm | 965770395 | 1,043915395 | 1,1201,015435 | 1,0581,300435 | 1,0581,300435 |
| | Net/Gross weight | kg | 62.5/66.5 | 72/76.5 | 106/111 | 117/126 | 112/127 |
| Refrigerant R-410A | | g | 1,650 | 2,200 | 2,600 | 3,550 | 4,200 |
| Throttle type | | | | | EXV&Capillary | | |
| Refrigerant piping | Liquid side/Gas side | mm | 6.35/12.7 | 9.53/16 | 9.53/16 | 9.53/16 | 9.53/16 |
Remark: The above design and specifications are subject to change without prior notice for product improvement.
DE - COMMISSIONING DISMANTLING & DISPOSAL
This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a danger and cause injury!
All work must only be carried out by competent persons using suitable protective clothing and safety precautions.
Read the Manual | Risk of electric shock | Unit is remotely controlled and |
| | may start without warning |
1.Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure that all points of electrical and gas isolation are secured in the OFF position. The supply cables and gas pipework may then be disconnected and removed. For points of connection refer to unit installation instructions.
2. Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then be reused, if appropriate, or returned to the manufacturer for disposal. Under No circumstances should refrigerant be vented to atmosphere. Where appropriate, drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing disposal of oily wastes.
3.Packaged unit can generally be removed in one piece after disconnection as above. Any fixing down bolts should be removed and then unit lifted from position using the points provided and equipment of adequate lifting capacity. Reference MUST be made to the unit installation instructions for unit weight and correct methods of lifting. Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above.
4.After removal from position the unit parts may be disposed of according to local laws and regulations.