DCA-125USJ — LOAD APPLICATION

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

If wattage is not given on the equipment's name plate,

NOTE approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 4 below when connecting loads.

 

 

 

Table 4. Power Factor By Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type Of Load

 

 

 

 

Power Factor

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-phase induction motors

 

0.4 - 0.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric heaters, incandescent

 

1.0

 

 

 

 

lamps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fluorescent lamps, mercury lamps

 

0.4 - 0.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic devices, communication

 

1.0

 

 

 

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 5. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current in

Load In Watts

 

 

 

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amperes

At 120

 

At 240

 

#10 Wire

 

#12 Wire

#14 Wire

 

#16 Wire

 

 

 

Volts

 

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

 

600

 

1000 ft.

 

600

ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

600

 

1200

 

500

ft.

 

300

ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5

900

 

1800

 

350

ft.

 

200

ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

1200

 

2400

 

250

ft.

 

150

ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

1800

 

3600

 

150

ft.

 

100

ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

2400

 

4800

 

125

ft.

 

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

If 3Ø load (kVA) is not given on the equipment nameplate,

NOTEapproximate 3Ø load output maybedeterminedbymultiplying voltage by amperage by 1.732.

Motors and motor-driven

NOTEequipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 5.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER - ELECTRICAL SYSTEM HAZARDS

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 27

Image 27
Contents Model DCA125USJ 2 DCA-125USJ Operation and Parts Manual REV. #2 01/27/11 DCA-125USJ Operation and Parts Manual REV. #2 01/27/11 Table of Contents Ordering parts has never been easier Parts Ordering ProceduresGenerator Specifications DCA-125USJ SpecificationsDimensions DCA-125USJ Dimensions TOP, Side and FrontSafety Messages DCA-125USJ Safety Informationfirst aid kit DCA-125USJ Safety Information„ Always know the location of the nearest fire extinguisherIf operating in speed ranges above the maximum allowable Before servicing equipment„ Never use fuel as a cleaning agent 3ECURE Portable Power Cables in Cable Tray with TIE wrapsFrom fuel vapors or if fuel is spilled on a hot engine „ Never use gas piping as an electrical ground Device. All installations should beDCA-125USJ Safety Information DCA-125USJ Generator Decals DCA-125USJ Generator Decals Typical Generator Grounding Application DCA-125USJ InstallationMounting DCA-125USJ InstallationOutdoor Installation Indoor InstallationControl Box DCA-125USJ Series Familiarization GeneratorEngine Operating Panel Generator Control PanelGenerator Major Components DCA-125USJ Major Components20 DCA-125USJ Operation and Parts Manual REV. #2 01/27/11 DCA-125USJ Generator Control Panel DCA-125USJ Engine Operating Panel DCA-125USJ Engine Operating Panel Output Terminal Familiarization DCA-125USJ Output Terminal Panel FamiliarizationTwist Lock Dual Voltage 120/240 VAC Receptacles 120VAC Gfci ReceptaclesBlower Fan Connecting LoadsMotors and motor-driven Single Phase LoadThree Phase Load DCA-125USJ Load ApplicationGfci Receptacle Load Capability Voltage Selector SwitchGenerator OutputVoltages Generator AmperageHow to Read the OutputTerminal Gauges DCA-125USJ Gauge ReadingReading Amperage 3Ø 208V/1Ø120V Output Terminal Lug Voltages DCA-125USJ Output Terminal Panel ConnectionsUvwo Terminal Output Voltages 3Ø 240/139 Output Terminal Lug Voltages1Ø 240V/120V Output Terminal Lug Voltages 3Ø 480/277 Output Terminal Lug VoltagesFuel Check DCA-125USJ PRE-SETUPCircuit Breakers Lubrication OilRefueling Refueling ProcedureMust be less than 50% Cleaning the RadiatorAir Cleaner Fan Belt Tension Operation FreezingWeatherAlternator BatteryBattery Cable Installation WiringStarting Manual Before StartingEngines exhaust contains harmful emissions Direct exhaust away from nearby personnelFrequency Meter Hz Starting Auto Mode Place the Mpec Control Switch in the Auto positionIs placed in the Auto position Emergency Shutdown Procedure Normal Shutdown ProcedureDCA-125USJ Maintenance Replacing Fuel Filter Air RemovalCheck Oil Level Replacing Oil FilterTo ensure adequate starting Battery chargerHydraulic Surge Brakes DCA-125USJ -TRAILER Brakes MaintenanceBrake Adjustment BrakesTires/Wheels/Lug Nuts SuspensionTire Wear/Inflation DCA-125USJ -TRAILER Maintenance Lug Nut Torque RequirementsStart all wheel lug nuts by hand DCA-125USJ -TRAILERWIRING Diagram Generator Wiring Diagram DCA-125USJ Generatorwiring DiagramDCA-125USJ Enginewiring Diagram DCA-125USJ -TROUBLESHOOTING Generator Engine Controller Troubleshooting Mpec DCA-125USJ -TROUBLESHOOTING Engine ControllerDCA-125USJ Operation and Parts Manual REV. #2 01/27/11 QTY. Column DCA-125USJ Explanation of Code in Remarks ColumnQty Description DCA-125USJ Suggested Spare PartsDCA-125USJ Generator Assy DCA-125USJ Generator Assy DCA-125USJ Control BOX Assy LAF3630010393P M32130007020330000180 060180882358 DCA-125USJ Operation and Parts Manual REV. #2 01/27/11 DCA-125USJ Control BOX Assy DCA-125USJ Engine and Radiator Assy 0602042594 M39232000540602041292 RE504836Engine & Radiator Assy 0603306590 06055151970602022563 0602022561DCA-125USJ Outputterminal Assy DCA-125USJ Outputterminal Assy DCA-125USJ Battery Assy M9103000504 06022201964D-2 M9310500404DCA-125USJ Muffler Assy M3333200304 M33301004020017112030 M3333000903DCA-125USJ Fueltank Assy 0605516090 M33630014020605505070 0605501074Enclosure #1 Assy DCA-125USJ Enclosure #1 Assy0603306797 M3413001812M3363300303 001691003074 DCA-125USJ Operation and Parts Manual REV. #2 01/27/11 25A 0030014000 24A M349320061424A M3493201204 0010114040Enclosure #2 Assy DCA-125USJ Enclosure #2 AssyM3443000904 M3443000802M3443000812 M3493303203DCA-125USJ Rubber Seals Assy 0228900660 02292008700229201130 0229201240DCA-125USJ Nameplate and Decals Assy M15000070 M1550000204M15000020 M1550000703Freight Policy Terms and Conditions of Sale PartsDCA-125USJ Operation and Parts Manual REV. #2 01/27/11 HERE’S HOW to GET Help

DCA125USJ specifications

The Multiquip DCA125USJ is a robust, high-performance generator designed to meet the diverse needs of various industries, including construction, events, and emergency backup. This generator boasts a compact size and impressive output, making it a reliable choice for both temporary and permanent power solutions.

At the heart of the DCA125USJ is a powerful diesel engine, providing an impressive 125 kVA output. This engine is engineered for efficiency, ensuring that the generator can continuously deliver reliable power while maintaining low operational costs. The generator operates at low RPM, which not only extends the engine's lifespan but also reduces noise levels, making it ideal for urban environments and sensitive locations.

One of the standout features of the DCA125USJ is its advanced electronic control system. This technology allows for seamless monitoring and management of the generator's performance, ensuring optimal operation. The control panel is user-friendly, offering real-time data on voltage, frequency, and operating hours, which simplifies maintenance and troubleshooting.

The DCA125USJ is equipped with a sturdy, weather-resistant enclosure that protects it from the elements, making it suitable for outdoor applications. This enclosure also contributes to noise reduction, ensuring quieter operation compared to traditional generators. Additionally, its compact design allows for easy transport and installation, making it a versatile option for various job sites.

Safety is a top priority in the design of the DCA125USJ. It features multiple safety mechanisms, such as an automatic shut-off system that activates in the event of low oil pressure or overheating, protecting the generator and prolonging its operational life.

Moreover, the DCA125USJ is compliant with rigorous emissions standards, making it an environmentally responsible choice. It offers options for multiple voltage outputs, which adds to its adaptability for different applications, from powering heavy machinery to providing electricity for small tools.

In summary, the Multiquip DCA125USJ stands out for its powerful diesel engine, state-of-the-art electronic controls, robust construction, and focus on safety and efficiency. Whether used in construction, outdoor events, or as a backup power source, the DCA125USJ is engineered to deliver reliable performance in a user-friendly package. This makes it a top contender for anyone needing dependable generator capabilities.