Multiquip DCA125USJ Operation FreezingWeather, Must be less than 50%, Cleaning the Radiator

Page 34

DCA-125USJPRE-SETUP

Coolant (John Deere Antifreeze/Summer Coolant/Water)

John Deere recommends John Deere Antifreeze/Summer Coolant for use in thier engines, which can be purchased in concentrate (and mixed with 50% demineralized water) or pre-diluted. See the John Deere Engine Owner's Manual for further details.

WARNING - BURN HAZARDS

If adding coolant/antifreeze mix to the radiator, DO NOT remove the radiator cap until the unit has completely cooled. The possibility of hot! coolant exists which can cause severe burns.

Ifaddingcoolant/antifreeze mix to the radiator, DO NOT remove the radiator cap until the unit has completely cooled. The possibility of hot! coolant exists which can cause severe burns.

Day-to-day addition of coolant is done from the recovery tank. When adding coolant to the radiator, DO NOT remove the radiator cap until the unit has completely cooled. See Table 11 for engine, radiator, and recovery tank coolant capacities. Make sure the coolant level in the recovery tank is always between the "H" and the "L" markings.

Table 11. Coolant Capacity

Engine and Radiator

4.4 Gal. (16.8 liters)

 

 

Reserve Tank

2 Quarts (1.9 liters)

 

 

Operation FreezingWeather

NOTE

When the antifreeze is mixed with

 

water, the antifreeze mixing ratio

 

must be less than 50%.

Cleaning the Radiator

The engine may overheat if the radiator fins become overloaded with dust or debris. Periodically clean the radiator fins with compressed air. Cleaning inside the machine is dangerous, so clean only with the engine turned off and the negative battery terminal disconnected.

Air Cleaner

Periodic cleaning/replacement is necessary. Inspect it in accordance with the John Deere Engine Owner's Manual.

Fan Belt Tension

A slack fan belt may contribute to overheating, or to insufficient charging of the battery. Inspect the fan belt for damage and wear and adjust it in accordance with the John

Deere Engine Owner's Manual.

The fan belt tension is proper if the fan belt bends 10 to 15

mm(Figure 37) when depressed with the thumb as shown below.

Figure 37. Fan Belt Tension

When operating in freezing weather, be certain the proper amount of antifreeze (Table 12) has been added.

Table 12. Anti-Freeze

Operating Temperatures

Vol %

Freezing Point

 

 

Anti-Freeze

 

 

°C

°F

 

 

 

 

50

-37

-34

 

 

 

CAUTION - ROTATING PARTS

NEVER place hands near the belts or fan while the generator set is running.

PAGE 34 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)

Image 34
Contents Model DCA125USJ 2 DCA-125USJ Operation and Parts Manual REV. #2 01/27/11 DCA-125USJ Operation and Parts Manual REV. #2 01/27/11 Table of Contents Parts Ordering Procedures Ordering parts has never been easierDCA-125USJ Specifications Generator SpecificationsDCA-125USJ Dimensions TOP, Side and Front DimensionsDCA-125USJ Safety Information Safety Messagesfire extinguisher DCA-125USJ Safety Information„ Always know the location of the nearest first aid kitBefore servicing equipment If operating in speed ranges above the maximum allowable3ECURE Portable Power Cables in Cable Tray with TIE wraps „ Never use fuel as a cleaning agentFrom fuel vapors or if fuel is spilled on a hot engine Device. All installations should be „ Never use gas piping as an electrical groundDCA-125USJ Safety Information DCA-125USJ Generator Decals DCA-125USJ Generator Decals DCA-125USJ Installation Typical Generator Grounding ApplicationIndoor Installation DCA-125USJ InstallationOutdoor Installation MountingGenerator Control Panel DCA-125USJ Series Familiarization GeneratorEngine Operating Panel Control BoxDCA-125USJ Major Components Generator Major Components20 DCA-125USJ Operation and Parts Manual REV. #2 01/27/11 DCA-125USJ Generator Control Panel DCA-125USJ Engine Operating Panel DCA-125USJ Engine Operating Panel DCA-125USJ Output Terminal Panel Familiarization Output Terminal Familiarization120VAC Gfci Receptacles Twist Lock Dual Voltage 120/240 VAC ReceptaclesConnecting Loads Blower FanDCA-125USJ Load Application Single Phase LoadThree Phase Load Motors and motor-drivenGenerator Amperage Voltage Selector SwitchGenerator OutputVoltages Gfci Receptacle Load CapabilityDCA-125USJ Gauge Reading How to Read the OutputTerminal GaugesReading Amperage 3Ø 240/139 Output Terminal Lug Voltages DCA-125USJ Output Terminal Panel ConnectionsUvwo Terminal Output Voltages 3Ø 208V/1Ø120V Output Terminal Lug Voltages3Ø 480/277 Output Terminal Lug Voltages 1Ø 240V/120V Output Terminal Lug VoltagesLubrication Oil DCA-125USJ PRE-SETUPCircuit Breakers Fuel CheckRefueling Procedure RefuelingOperation FreezingWeather Cleaning the RadiatorAir Cleaner Fan Belt Tension Must be less than 50%Wiring BatteryBattery Cable Installation AlternatorDirect exhaust away from nearby personnel Before StartingEngines exhaust contains harmful emissions Starting ManualFrequency Meter Hz Place the Mpec Control Switch in the Auto position Starting Auto ModeIs placed in the Auto position Normal Shutdown Procedure Emergency Shutdown ProcedureDCA-125USJ Maintenance Replacing Oil Filter Air RemovalCheck Oil Level Replacing Fuel FilterBattery charger To ensure adequate startingBrakes DCA-125USJ -TRAILER Brakes MaintenanceBrake Adjustment Hydraulic Surge BrakesSuspension Tires/Wheels/Lug NutsTire Wear/Inflation Lug Nut Torque Requirements DCA-125USJ -TRAILER MaintenanceStart all wheel lug nuts by hand DCA-125USJ -TRAILERWIRING Diagram DCA-125USJ Generatorwiring Diagram Generator Wiring DiagramDCA-125USJ Enginewiring Diagram DCA-125USJ -TROUBLESHOOTING Generator DCA-125USJ -TROUBLESHOOTING Engine Controller Engine Controller Troubleshooting MpecDCA-125USJ Operation and Parts Manual REV. #2 01/27/11 DCA-125USJ Explanation of Code in Remarks Column QTY. ColumnDCA-125USJ Suggested Spare Parts Qty DescriptionDCA-125USJ Generator Assy DCA-125USJ Generator Assy DCA-125USJ Control BOX Assy 0601808823 M32130007020330000180 LAF3630010393P58 DCA-125USJ Operation and Parts Manual REV. #2 01/27/11 DCA-125USJ Control BOX Assy DCA-125USJ Engine and Radiator Assy RE504836 M39232000540602041292 0602042594Engine & Radiator Assy 0602022561 06055151970602022563 0603306590DCA-125USJ Outputterminal Assy DCA-125USJ Outputterminal Assy DCA-125USJ Battery Assy M9310500404 06022201964D-2 M9103000504DCA-125USJ Muffler Assy M3333000903 M33301004020017112030 M3333200304DCA-125USJ Fueltank Assy 0605501074 M33630014020605505070 0605516090DCA-125USJ Enclosure #1 Assy Enclosure #1 Assy0016910030 M3413001812M3363300303 060330679774 DCA-125USJ Operation and Parts Manual REV. #2 01/27/11 0010114040 24A M349320061424A M3493201204 25A 0030014000DCA-125USJ Enclosure #2 Assy Enclosure #2 AssyM3493303203 M3443000802M3443000812 M3443000904DCA-125USJ Rubber Seals Assy 0229201240 02292008700229201130 0228900660DCA-125USJ Nameplate and Decals Assy M1550000703 M1550000204M15000020 M15000070Terms and Conditions of Sale Parts Freight PolicyDCA-125USJ Operation and Parts Manual REV. #2 01/27/11 HERE’S HOW to GET Help

DCA125USJ specifications

The Multiquip DCA125USJ is a robust, high-performance generator designed to meet the diverse needs of various industries, including construction, events, and emergency backup. This generator boasts a compact size and impressive output, making it a reliable choice for both temporary and permanent power solutions.

At the heart of the DCA125USJ is a powerful diesel engine, providing an impressive 125 kVA output. This engine is engineered for efficiency, ensuring that the generator can continuously deliver reliable power while maintaining low operational costs. The generator operates at low RPM, which not only extends the engine's lifespan but also reduces noise levels, making it ideal for urban environments and sensitive locations.

One of the standout features of the DCA125USJ is its advanced electronic control system. This technology allows for seamless monitoring and management of the generator's performance, ensuring optimal operation. The control panel is user-friendly, offering real-time data on voltage, frequency, and operating hours, which simplifies maintenance and troubleshooting.

The DCA125USJ is equipped with a sturdy, weather-resistant enclosure that protects it from the elements, making it suitable for outdoor applications. This enclosure also contributes to noise reduction, ensuring quieter operation compared to traditional generators. Additionally, its compact design allows for easy transport and installation, making it a versatile option for various job sites.

Safety is a top priority in the design of the DCA125USJ. It features multiple safety mechanisms, such as an automatic shut-off system that activates in the event of low oil pressure or overheating, protecting the generator and prolonging its operational life.

Moreover, the DCA125USJ is compliant with rigorous emissions standards, making it an environmentally responsible choice. It offers options for multiple voltage outputs, which adds to its adaptability for different applications, from powering heavy machinery to providing electricity for small tools.

In summary, the Multiquip DCA125USJ stands out for its powerful diesel engine, state-of-the-art electronic controls, robust construction, and focus on safety and efficiency. Whether used in construction, outdoor events, or as a backup power source, the DCA125USJ is engineered to deliver reliable performance in a user-friendly package. This makes it a top contender for anyone needing dependable generator capabilities.