LOAD APPLICATION

SINGLE PHASE LOAD

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is infl uenced by the effi ciency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

THREE PHASE LOAD

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fl uorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA45SSIU3 50 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (12/19/08) — PAGE 25

Image 25
Contents This Manual Must Accompany the Equipment AT ALL Times Model DCA45SSIU3Proposition 65 Warning Administrator Reporting Safety DefectsDCA45SSIU3 Generator Table of ContentsOrdering parts has never been easier Parts Ordering ProceduresSafety Messages Safety InformationGenerator Safety General Safety Always know the location of the nearest Before servicing equipment Engine SafetyTowing Safety Fuel SafetyGrounding Safety Electrical SafetyPower Cord/Cable Safety  The electrical voltage required toEnvironmental Safety Battery SafetyGenerator Specifications SpecificationsDimensions DimensionsTypical Generator Grounding Application InstallationIndoor Installation Outdoor InstallationMounting Generator GroundingGeneral Information Item no Major ComponentsOwing from the U,V, and W Output Terminal Lugs to the load Generator Control PanelPage Fuel Gauge Indicates amount of diesel fuel available Engine Operating PanelPage Output Terminal Familiarization Output Terminal Panel FamiliarizationTerminal legs O and Ground are considered bonded grounds 200V Twist-Lock Auxiliary Receptacles VAC Gfci ReceptaclesOver Current Relay Connecting LoadsThree Phase Load Single Phase LoadLoad Application Voltage Selector Switch Locking Button Voltage Selector SwitchGenerator Outputs Generator Output VoltagesReading Voltage Generator OUTPUTS/GAUGE ReadingReading Amperage Uvwo Terminal Output Voltages Output Terminal Panel Connections3Ø-220/127 Uvwo Terminal Output Voltages 3Ø-200V/1Ø-115V Uvwo Terminal Output Voltages1Ø-200/100V Uvwo Terminal Output Voltages 3Ø-440/254V Uvwo Terminal Output VoltagesCircuit Breakers INSPECTION/SETUPLubrication OIL Fuel CheckOnly use #2 diesel fuel when refueling Refueling ProcedureAIR Cleaner FAN Belt Tension Cleaning the RadiatorCoolant ANTIFREEZE/SUMMER COOLANT/ Water Operation in Freezing WeatherBattery Cable Installation BatteryWiring AlternatorBefore Starting Generator START-UP ProcedureStarting Engine’s exhaust contains harmful emissionsFrequency Meter Normal Shutdown Procedure Generator SHUT-DOWN ProceduresEmergency Shutdown Procedure Never stop the engine suddenly except in an emergencyGeneral Inspection AIR Cleaner MaintenanceAir Cleaner with Dust Indicator Fuel Tank Inspection Fuel AdditionAIR Removal Check OIL Level Radiator CleaningReplacing Oil Filter Flushing OUT Radiator and Replacing CoolantTrailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Brakes Brake AdjustmentHydraulic Surge Brakes ActuatorTire Wear/Inflation TIRES/WHEELS/LUG NutsSuspension Never use an pneumatic air gun to tighten wheel lug nuts Lug Nut Torque RequirementsTrailer/Towing Vehicle Wiring Diagram Trailer Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramTroubleshooting Generator Explanation of Code in Remarks Column Sample Parts ListTo 3 units Suggested Spare PartsGenerator Assy 8051070003 B31101002020010310035 0042510000Control BOX Assy 0601870431 M1213000802FG3110WS02 3P 110A 0601870490Engine and Radiator Assy 8970497081 M19232000540605000048 0030010000Engine and Radiator Assy 0199900700 01500000180605515106 M9300000003Output Terminal Assy M9220100204 M1230700103M9220100104 0039310000Engine Operating Panel Assy 8944024980 89704441800602103092 2A# 0601810245Battery Assy 627MFD 0602220187M9310500014 M9103000304Muffler Assy M1330100703 M33301009020016910025 M1333001903Fuel Tank Assy 0605505070 M1363001602M1363200104 M9310500104Enclosure Assy M1413400004 M1413002902M1423001902 M1493106703Enclosure Assy Part Name QTY Rubber Seals Assy Seal Rubber Nameplate and Decals Assy M1550001304 M1550000204M1550002003 M1550002103Freight Policy Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help

CDA45SSIU3 specifications

The Multiquip CDA45SSIU3 is a versatile and powerful piece of equipment primarily designed for the construction and industrial sectors. As part of Multiquip's range of durable and reliable construction machinery, the CDA45SSIU3 is engineered to meet the demands of various tasks, including compacting soil, asphalt, and granular materials.

One of the standout features of the CDA45SSIU3 is its robust, high-performance engine. Powered by a reliable and efficient fuel system, the machine ensures optimal performance even under the heaviest loads. This not only improves productivity but also reduces fuel consumption, resulting in significant cost savings for contractors and operators.

The CDA45SSIU3 is equipped with advanced vibration technology, which provides exceptional compaction capabilities. Its dual-pump system delivers consistent performance, enabling operators to achieve the desired density in various soil types. This feature enhances the efficiency of the compaction process, making it ideal for preparing foundations, roadways, and other critical infrastructure.

Another notable characteristic of the CDA45SSIU3 is its user-friendly design. The machine comes with an intuitive control panel that allows operators to easily manage its functions. This ease of use reduces the learning curve for new operators, allowing them to quickly become proficient and maximizing productivity on job sites.

Durability is a key consideration in the design of the CDA45SSIU3. Constructed with high-quality materials, it withstands the rigors of demanding environments. The heavy-duty frame and components ensure longevity and consistent performance over time while minimizing maintenance requirements.

Additionally, the CDA45SSIU3 is designed with mobility in mind. Its compact dimensions and lightweight structure make it easy to transport between job sites. This portability ensures that operators can efficiently transition from one project to another without unnecessary delays.

Safety features are also a priority with the CDA45SSIU3. Equipped with safeguards that prevent accidental operation and enhance operator safety, the machine provides peace of mind while in use.

In summary, the Multiquip CDA45SSIU3 stands out as a powerful, reliable, and efficient solution for compaction tasks in construction and industrial applications. Its advanced engine, vibration technology, user-friendly controls, durable construction, and safety features make it an excellent choice for professionals seeking high-performance equipment. With the CDA45SSIU3, users can expect enhanced productivity, reduced operating costs, and reliable performance in various conditions.