GENERATOR CONTROL AND

OPERATION

Refer to the appropriate control panel operator’s manual for this unit.

OPERATING UNIT WITH MANUAL TRANSFER SWITCH

If the generator was installed in conjunction with a transfer switch capable of manual operation only, the following procedure applies. A manually operated transfer switch is one that will not provide automatic start-up and does not include an intelligence circuit.

‹ENGINE START-UP AND TRANSFER

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

DANGER

The Maintenance Disconnect Switch and the AUTO/OFF/MANUAL switches (if so equipped) must be set properly, or the generator will crank and start as soon as the utility power to the transfer switch is turned off. Refer to applicable control panel and transfer switch manuals for more information.

Do not proceed until certain that utility source voltage is available to the transfer switch and the transfer switch main contacts are set to

UTILITY.

Do not attempt manual operation until all power supplies to the transfer switch have been posi- tively turned off, or extremely dangerous - pos- sibly lethal - electrical shock will result.

Transfer switch enclosure doors should be kept closed and locked. Only authorized personnel should be allowed access to the transfer switch interior. Extremely high and dangerous voltages are present in the transfer switch.

In order to transfer load from the utility source to the generator, follow these directions:

Turn OFF or disconnect the utility power circuit to the transfer switch, using the means provided (such as the utility source main line circuit break- er).

Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to the utility power supply.

Set the standby generator’s main line circuit break- er to its OFF (or OPEN) position.

Start the generator.

Do not crank the engine continuously for longer than 30 seconds, or the heat may

damage the starter motor.

Let engine stabilize and warm up.

Check all applicable instrument and gauge read- ings. When certain that all readings are correct, move the transfer switch manual handle to its STANDBY (GENERATOR) position, i.e., load cir- cuits supplied by the generator.

Set the standby generator’s main line circuit break- er to its ON (or CLOSED) position.

Load circuits are now powered by the standby generator.

‹RETRANSFER AND SHUTDOWN

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

To transfer the load back to the utility power source and shut down the generator, follow these direc- tions:

Set the standby generator’s main line circuit break- er to its OFF (or OPEN) position.

Manually move the transfer switch handle to its UTILITY (NORMAL) position, i.e., load circuits connected to the utility.

Turn ON the utility power supply to the transfer switch, using the means provided (such as the util- ity power source main line circuit breaker).

Let the generator run at no-load for a few minutes to stabilize internal temperatures.

Shut down the generator.

OPERATING UNIT WITH AUTOMATIC TRANSFER SWITCH

If the generator has been installed with an automatic transfer switch, such as an RTS, HTS, or GTS-type transfer switch, the engine may be started and stopped automatically or manually.

NOTE:

Refer to the applicable manual for your trans- fer switch and to “Transfer Switch Start Signal Connections”. In addition, please note the dangers under “Engine Start-up and Transfer.”

9-1

08/05

0 .Rev Oper001

Image 15
Contents Centurion Standby Generator Sets Table of Contents  Warning   Electrical Hazards  Introduction ‹ Operation and Maintenance‹ HOW to Obtain Service Authorized Service Dealer Location‹ Data Label Identification RecordEquipment Description Engine OIL RecommendationsCoolant Recommendations Engine Protective Devices ‹ LP Fuel System Fuel System‹ Fuel Requirements ‹ Natural GAS Fuel SystemSpecifications ‹ Cold Weather KIT ‹ Reconfiguring the Fuel SystemGenerator AC Lead Connections Alternator Power Winding Connections‹ FOUR-LEAD, SINGLE-PHASE Stator ‹ 3-PHASE AlternatorsInstallation Preparation Before START-UPInitial Inspection for QT Genset Startup START-UP Checklist ‹ Preparation for START-UP‹ START-UP Inspection ‹ Retransfer and Shutdown Operating Unit with Manual Transfer SwitchGenerator Control Operation ‹ Engine START-UP and TransferChecking Fluid Levels Cooling SystemMaintenance Owner Operator can Perform Miscellaneous Maintenance Repair Parts ‹ Battery Maintenance‹ Battery Replacement KW 150 KW Standby GAS Engine Driven Generator Sets Service ScheduleMaintenance Level 11-3 11-4 Problem Cause Correction Troubleshooting GuideStandby Generator Sets Standby Generator Sets Standby Generator Sets Page PAN CB Conn BOX Page Assy RTR 390 30KD1 CPL Page MTG Base 3.9L 40KW C2 Page Tray Battery Page Flexplate HSB 3.9L Chrysler 1800RPM Page Encl HSB Control Panel Page Weldment RAD Support 3.9L C2 Page Pipe R/H Side Muffler Page Element AIR Filter Page Flange Fuel Inlet Page Rear Wrap C2 Page Page Page Page Page Page Standby Generator Sets Warranty

005223-0 specifications

Generac Power Systems has established itself as a prominent name in the field of power generation, and the Generac 005223-0 model exemplifies the company's commitment to innovative technology and reliable performance. This portable generator is designed for various applications, from home backup power to outdoor events, ensuring users have access to electricity when they need it the most.

One of the standout features of the Generac 005223-0 is its impressive power output. With a capacity that typically exceeds 3000 watts, this generator can handle essential home appliances, tools, and more, providing peace of mind during power outages or when electricity is required away from a stationary power source. The generator is equipped with a powerful, efficient engine that optimizes fuel consumption while delivering maximum performance.

In addition to its robust power capabilities, the 005223-0 incorporates Generac’s patented PowerRush technology, which enhances the starting capacity, allowing users to start larger loads such as air conditioners or power tools without any issue. This technology significantly increases the generator’s output upon startup, making it an excellent choice for users needing to power multiple devices simultaneously.

Safety is a primary concern for Generac, and the 005223-0 exemplifies this commitment through its built-in protection features. The generator includes low-oil shutdown, which automatically turns off the engine when the oil level drops too low, preventing damage and ensuring longevity. Furthermore, the unit is designed with a sturdy frame to withstand various conditions, making it suitable for both residential and commercial use.

Another notable characteristic of the 005223-0 is its user-friendly interface. The generator's control panel is intuitively laid out, providing easy access to power settings, fuel gauge, and various output options. This makes operation straightforward, even for those who are not well-versed in generator technology.

Lastly, portability is a key feature of the Generac 005223-0, as it is designed with rugged wheels and a lightweight structure, enabling easy transportation to different locations. Whether it’s for outdoor gatherings, camping trips, or emergency backup, this generator is exceptional in versatility and reliability. With the 005223-0, users can expect a seamless power solution backed by Generac’s reputation for quality and service.