Fuel Systems

FUEL SYSTEM

‹FUEL REQUIREMENTS

The standby generator may be equipped with one of the following fuel systems:

Natural gas fuel system

Propane vapor (PV) fuel system

The Manual Drawing Listing that is affixed to the unit includes the “Identification Code,” which may be used to identify the type of fuel system installed on the unit.

Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.

Required fuel pressure for natural gas is 5 inches to 14 inches water column (0.18 to 0.5 psi); and for liquid propane, 5 inches to 14 inches of water column (0.18 to 0.5 psi).

NOTE:

Any piping used to connect the generator to the fuel supply should be of adequate size to ensure the fuel pressure NEVER drops below five inches water column for natural gas or 5 inches water column for propane vapor for all load ranges.

NOTE:

It is the responsibility of the installer to make sure that only the correct recommended fuel is sup- plied to the generator fuel system. Thereafter, the owner/operator must make certain that only the proper fuel is supplied.

‹NATURAL GAS FUEL SYSTEM

Natural gas is supplied in its vapor state. In most cases, the gas distribution company provides piping from the main gas distribution line to the standby generator site. The following information applies to natural gas fuel systems.

Gas pressure in a building is usually regulated by national, state and local codes.

To reduce gas pressure to a safe level before the gas enters a building, a primary regulator is needed. The natural gas supplier may or may not supply such a regulator.

It is the responsibility of the gas supplier to make sure sufficient gas pressure is available to operate the primary regulator.

Gas pressure at the inlet to the fuel shutoff sole- noid should not exceed approximately 14 inches water column (0.5 psi). Optimum pressure at the fuel shutoff solenoid is 11 inches water column (0.4 psi).

‹PROPANE VAPOR WITHDRAWAL FUEL SYSTEM

This type of system utilizes the vapors formed above the liquid fuel in the supply tank. Approximately 10 to 20 percent of the tank capacity is needed for fuel expansion from the liquid to the vapor state. The vapor withdrawal system is generally best suited for smaller engines that require less fuel. The installer should be aware of the following:

The natural gas and LP gas systems are similar. However, the natural gas system delivers gas at a pressure of approximately five inches water col- umn to the carburetor.

When ambient temperatures are low and engine fuel consumption is high, the vapor withdrawal system may not function efficiently.

Ambient temperatures around the supply tank must be high enough to sustain adequate vaporiza- tion, or the system will not deliver the needed fuel volume.

In addition to the cooling effects of ambient air, the vaporization process itself provides an additional cooling effect.

‹LP FUEL SYSTEM

LP is supplied as a liquid in pressure tanks. It is usually made up of propane, butane, or a mixture of the two gases. Propane tends to vaporize readily even at temperatures as low as -20° F (-29° C). However, butane reverts to its liquid state when temperatures drop below 32° F (0° C).

LP in a liquid withdrawal system must be converted to its gaseous state before it is introduced into the engine carburetor. A vaporizer-converter is generally used to accomplish this. In such a converter, heated engine coolant is ported through the converter to provide the necessary heat for conversion of the fuel from a liquid to a gaseous state.

5-1

08/05

0 .Rev FuelSys001

Image 9
Contents Centurion Standby Generator Sets Table of Contents  Warning   Electrical Hazards  ‹ HOW to Obtain Service ‹ Operation and MaintenanceAuthorized Service Dealer Location Introduction‹ Data Label Identification RecordEquipment Description Engine OIL RecommendationsCoolant Recommendations Engine Protective Devices ‹ Fuel Requirements Fuel System‹ Natural GAS Fuel System ‹ LP Fuel SystemSpecifications ‹ Cold Weather KIT ‹ Reconfiguring the Fuel System‹ FOUR-LEAD, SINGLE-PHASE Stator Alternator Power Winding Connections‹ 3-PHASE Alternators Generator AC Lead ConnectionsInstallation Preparation Before START-UPInitial Inspection for QT Genset Startup START-UP Checklist ‹ Preparation for START-UP‹ START-UP Inspection Generator Control Operation Operating Unit with Manual Transfer Switch‹ Engine START-UP and Transfer ‹ Retransfer and ShutdownChecking Fluid Levels Cooling SystemMaintenance Owner Operator can Perform Miscellaneous Maintenance Repair Parts ‹ Battery Maintenance‹ Battery Replacement KW 150 KW Standby GAS Engine Driven Generator Sets Service ScheduleMaintenance Level 11-3 11-4 Problem Cause Correction Troubleshooting GuideStandby Generator Sets Standby Generator Sets Standby Generator Sets Page PAN CB Conn BOX Page Assy RTR 390 30KD1 CPL Page MTG Base 3.9L 40KW C2 Page Tray Battery Page Flexplate HSB 3.9L Chrysler 1800RPM Page Encl HSB Control Panel Page Weldment RAD Support 3.9L C2 Page Pipe R/H Side Muffler Page Element AIR Filter Page Flange Fuel Inlet Page Rear Wrap C2 Page Page Page Page Page Page Standby Generator Sets Warranty

005223-0 specifications

Generac Power Systems has established itself as a prominent name in the field of power generation, and the Generac 005223-0 model exemplifies the company's commitment to innovative technology and reliable performance. This portable generator is designed for various applications, from home backup power to outdoor events, ensuring users have access to electricity when they need it the most.

One of the standout features of the Generac 005223-0 is its impressive power output. With a capacity that typically exceeds 3000 watts, this generator can handle essential home appliances, tools, and more, providing peace of mind during power outages or when electricity is required away from a stationary power source. The generator is equipped with a powerful, efficient engine that optimizes fuel consumption while delivering maximum performance.

In addition to its robust power capabilities, the 005223-0 incorporates Generac’s patented PowerRush technology, which enhances the starting capacity, allowing users to start larger loads such as air conditioners or power tools without any issue. This technology significantly increases the generator’s output upon startup, making it an excellent choice for users needing to power multiple devices simultaneously.

Safety is a primary concern for Generac, and the 005223-0 exemplifies this commitment through its built-in protection features. The generator includes low-oil shutdown, which automatically turns off the engine when the oil level drops too low, preventing damage and ensuring longevity. Furthermore, the unit is designed with a sturdy frame to withstand various conditions, making it suitable for both residential and commercial use.

Another notable characteristic of the 005223-0 is its user-friendly interface. The generator's control panel is intuitively laid out, providing easy access to power settings, fuel gauge, and various output options. This makes operation straightforward, even for those who are not well-versed in generator technology.

Lastly, portability is a key feature of the Generac 005223-0, as it is designed with rugged wheels and a lightweight structure, enabling easy transportation to different locations. Whether it’s for outdoor gatherings, camping trips, or emergency backup, this generator is exceptional in versatility and reliability. With the 005223-0, users can expect a seamless power solution backed by Generac’s reputation for quality and service.