Generac Power Systems COMMERCIAL SERIES manual KW Rating Engine Size, Engine Cooling, Exhaust

Page 3

COMMERCIAL 60 kW

COMMERCIAL SERIES

OPERATING DATA

 

 

 

COMMERCIAL 60 kW

 

KW RATING

 

 

60

 

 

 

 

 

 

ENGINE SIZE

 

 

3.0 Liter V-6

 

 

 

 

 

 

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

 

KW

AMP

CB Size

120/240V, single phase, 1.0 pf

 

60

250

300

120/208V, 3-phase, 0.8 pf

 

60

208.4

250

120/240V, 3-phase, 0.8 pf

 

60

180.6

200

277/480V, 3-phase, 0.8 pf

 

60

90.3

100

 

 

 

 

 

GENERATOR LOCKED ROTOR KVA

 

 

 

 

AVAILABLE @ VOLTAGE DIP OF 35%

 

 

 

 

Single phase or 208V & 240V 3-phase

 

 

120

 

480V 3-phase

 

 

141

 

 

 

 

 

 

ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)

 

Natural Gas

 

Propane

 

 

(ft3/hr.)

(gal/hr.)

cu ft/hr

Exercise cycle

 

123

1.34

48.7

25% of rated load

 

260

2.84

103.3

50% of rated load

 

500

5.46

198.6

75% of rated load

 

700

7.64

277.9

100% of rated load

 

960

10.48

381.3

 

 

 

 

 

ENGINE COOLING

ft3/min.

 

 

 

Air flow (inlet air including alternator and combustion air)

 

3,280

 

System coolant capacity

US gal.

 

2.5

 

Heat rejection to coolant

BTU/hr.

 

270,000

 

Max. operating air temp. on radiator

°C (°F)

 

60 (150)

 

Max. ambient temperature

°C (°F)

 

50 (140)

 

 

 

 

 

 

COMBUSTION AIR REQUIREMENTS

 

 

 

 

Flow at rated power 60 Hz

cfm

 

180

 

 

 

 

 

 

SOUND EMISSIONS IN DBA

 

 

 

 

db(A) @ 23 feet in exercise mode

 

 

63

 

db(A) @ 23 feet at normal operating load

 

 

71

 

 

 

 

 

 

EXHAUST

 

 

 

 

Exhaust flow at rated output 60 Hz

cfm

 

494

 

Exhaust temp. at muffler outlet

°F

 

1,050

 

 

 

 

 

 

ENGINE PARAMETERS

 

 

 

 

Rated synchronous RPM

60 Hz

 

3600

 

HP at rated KW

60 Hz

 

94

 

 

 

 

 

 

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

 

 

 

 

Temperature Deration

 

 

 

 

3% for every 10 °C above - °C

 

25

 

1.65% for every 10 °F above - °F

 

77

 

Altitude Deration

 

 

 

 

1% for every 100 m above - m

 

183

 

3% for every 1000 ft. above - ft.

 

600

 

 

 

 

 

 

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.

Image 3
Contents 60 kW 60 Hz FeaturesGovernor Specifications Engine SpecificationsGenerator Features Control Panel FeaturesCombustion AIR Requirements KW Rating Engine SizeGenerator Locked Rotor KVA Available @ Voltage DIP of 35% Engine CoolingInterconnections

COMMERCIAL SERIES specifications

Generac Power Systems has established itself as a leader in the field of power generation, offering a diverse range of products designed to meet various energy needs. Among its notable offerings is the Commercial Series, specially engineered to provide reliable backup power solutions for businesses and commercial facilities. The Commercial Series is known for its robust construction, advanced technologies, and versatile applications.

One of the main features of the Generac Commercial Series is its exceptional power output capabilities. These generators range in size and can deliver from 22 kW to 150 kW, making them suitable for small businesses to large industrial operations. Their capability to run high-demand operations ensures that essential services remain uninterrupted during power outages.

The Commercial Series utilizes advanced engine technology, providing durability and longevity. Generac’s proprietary engines are specifically designed for commercial use, delivering reliable starting and performance. These engines are also built with a robust cooling system to handle extended running periods efficiently.

Another key characteristic of the Commercial Series is its user-friendly interface. The generators come equipped with an intuitive control panel that allows operators to manage and monitor the system with ease. Features such as automatic start and shut-off ensure that the generator operates seamlessly when utility power is lost, providing peace of mind to business owners.

The Commercial Series also prioritizes safety through a variety of integrated features. Automatic voltage regulation and circuit protection help safeguard equipment from potential damage caused by surges or fluctuations in power. Additionally, Generac’s generators are designed to operate quietly, ensuring minimal disruption to business operations and surrounding areas.

Connectivity is a highlight of the Commercial Series, with many models featuring remote monitoring capabilities. With Generac's Mobile Link technology, users can monitor their generator's status from anywhere using a smartphone, tablet, or computer. This feature adds a level of convenience by allowing users to stay informed about their power system without being onsite.

Fuel flexibility is another significant characteristic, as Generac offers models that can operate on natural gas, propane, or diesel. This versatility allows businesses to choose the fuel source that best fits their operational needs and sustainability goals.

In summary, Generac Power Systems’ Commercial Series combines powerful performance, advanced technology, user-friendly operation, robust safety features, and flexible fuel options. This comprehensive range of capabilities makes it an ideal choice for businesses seeking reliable backup power solutions to protect their operations and ensure resilience in the face of unexpected outages.