Generac Power Systems 005261-1, 005262-1 owner manual Cooling System, Checking Fluid Levels

Page 16

Standby Generator Sets

Maintenance

MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES

Before working on the generator, ensure the fol- lowing:

The AUTO/OFF/MANUAL switch is in the OFF position.

The 15A fuse has been removed from the con- trol box.

The 120VAC supply to the battery charger is switched OFF.

‹EVERY THREE MONTHS

1.Check battery condition.

2.Inspect and test fuel system.

3.Check transfer switch.

4.Inspect exhaust system.

5.Check engine ignition system.

6.Check fan belts.

‹ONCE EVERY SIX MONTHS

1.Test Engine Safety Devices (low oil pressure, low coolant level, high coolant temperature).

‹ONCE ANNUALLY

1.Test engine governor; adjust or repair, if needed.

2.Clean, inspect generator.

3.Flush cooling system.

COOLING SYSTEM

Air intake and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down. (See the installation diagram.)

The exhaust system parts from this product get extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL SYSTEM

Engine cranking, start up and running are controlled by a solid state Engine Controller circuit board. Battery voltage is delivered to that circuit board via a 15 amp fuse. These overcurrent protection devices will open if the circuit is overloaded.

If a circuit breaker opens or a fuse element melts, find the cause of the overload before resetting the circuit breaker or replacing the fuse.

‹FIRST 30 OPERATING HOURS

1. Change engine "break-in" oil and filter.

‹FIRST 100 OPERATING HOURS

1.Change engine oil and oil filter. After initial change, service engine oil and filter at 100 operat- ing hours or six months, whichever comes first.

2.Retorque cylinder head.

3.Retorque intake and exhaust manifold.

‹EVERY 500 OPERATING HOURS

1.Service air cleaner.

2.Check starter.

3.Check engine DC alternator.

CHECKING FLUID LEVELS

‹CHECK ENGINE OIL

Check engine crankcase oil level (Figure 10.1) at least every 20 hours of operation, or prior to use.

Remove oil dipstick and wipe dry with a clean, lint- free cloth.

Install oil dipstick, then remove again.

Oil should be between FULL and ADD marks.

If oil level is below the dipstick ADD mark, remove oil fill cap-. Add the recommended oil to bring oil level up to the FULL mark. DO NOT FILL ABOVE THE “FULL” MARK. See “Engine Oil Recommen- dations” for recommended oils.

‹EVERY 800 OPERATING HOURS

1.Retorque cylinder head.

2.Retorque intake and exhaust manifold.

3.Check engine compression.

4.Check valve clearance.

10-1

04/06

0 .Rev Maint012

Image 16
Contents New standard of reliability Standby Generator Sets Table of Contents  Warning   Electrical Hazards  ‹ Operation and Maintenance ‹ HOW to Obtain ServiceAuthorized Service Dealer Location IntroductionIdentification Record ‹ Data LabelEngine OIL Recommendations Equipment DescriptionCoolant Recommendations Engine Protective Devices Fuel System ‹ Fuel Requirements‹ Natural GAS Fuel System ‹ LP Fuel SystemSpecifications ‹ Reconfiguring the Fuel System ‹ Cold Weather KITAlternator Power Winding Connections ‹ FOUR-LEAD, SINGLE-PHASE Stator‹ 3-PHASE Alternators Generator AC Lead ConnectionsPreparation Before START-UP InstallationInitial Inspection for QT Genset Startup ‹ Preparation for START-UP START-UP Checklist‹ START-UP Inspection Operating Unit with Manual Transfer Switch Generator Control Operation‹ Engine START-UP and Transfer ‹ Retransfer and ShutdownCooling System Checking Fluid LevelsMaintenance Owner Operator can Perform ‹ Changing Engine OIL ‹ Changing the Engine AIR Cleaner ‹ Coolant Change‹ Spark Plugs Miscellaneous Maintenance ‹ Cleaning the Generator‹ Battery ‹ Battery MaintenanceService Schedule KW 150 KW Standby GAS Engine Driven Generator SetsMaintenance Level 11-3 11-4 Troubleshooting Guide Problem Cause CorrectionStandby Generator Sets Page PAN CB Conn BOX Page UL Circuit Breaker QJ-2P Page Instr Hypot Test not Shown Page Components Included in 0F9696E Page Components Included in 0G1290E Page Weldment Frame 2.4L C2 Page Battery Tray C1 CPL Page Gasket Bosch 32 Page Engine 2.4L G2 Rework Page Weldment Radiator Support 2.4L Page Flange Fuel Inlet Page Rear Wrap C2 CPL Page Bracket Muffler Page Page Page Page Page Page Page Page Page Page Page C2 Units Standby Generator Sets Warranty

005261-1, 005262-1 specifications

Generac Power Systems, a leader in backup power solutions, offers a range of generators designed to meet different power needs. Among their notable products are the Generac models 005261-1 and 005262-1, which are both excellent options for residential and commercial applications. These generators are specifically designed to provide reliable power during outages, ensuring that homes and businesses remain operational when it matters most.

One of the standout features of the Generac 005261-1 and 005262-1 models is their automatic transfer switch technology. This feature allows the generators to detect power outages automatically and switch on within seconds, providing uninterrupted power. The systems are designed for ease of use, with a user-friendly control panel that displays critical information about the generator’s status and maintenance requirements.

Both models are powered by Generac's innovative engine technology, which ensures superior performance and fuel efficiency. The engines are engineered to run quietly while delivering ample power output. The 005261-1 typically offers up to 22 kW of backup power, while the 005262-1 goes up to 26 kW, making them suitable for larger homes or essential commercial applications.

In terms of construction, the Generac models feature durable weather-resistant enclosures, ensuring they can withstand harsh environmental conditions. Their compact design makes installation straightforward, with options for both concrete pads and low-profile installations. Furthermore, both generators are equipped with a state-of-the-art digital controller that allows users to monitor the system remotely.

Another important characteristic is the Generac Power Zone Mobile Link, which allows users to monitor their generator’s status via a smartphone app. This feature provides peace of mind, as users can receive alerts regarding power outages, routine maintenance, and operational status in real time, even when they are not home.

The maintenance of these generators is simplified by their built-in features, including an integrated maintenance reminder system that alerts users when service is due. This proactive approach aids in extending the life of the generator and optimizing performance over time.

In summary, the Generac Power Systems models 005261-1 and 005262-1 offer a blend of reliability, efficiency, and advanced technology. With automatic transfer switches, robust engine design, and smart monitoring capabilities, these generators stand out in the market as excellent choices for backup power needs. Whether for residential use or light commercial applications, users can trust in Generac’s commitment to delivering dependable power solutions.