Generac Power Systems 005261-1, 005262-1 owner manual Maintenance Owner Operator can Perform

Page 17

Standby Generator Sets

Maintenance

Figure 10.1 - Oil Dipstick and Oil Fill Cap

Oil Fill Cap

Oil

Dipstick

‹EXERCISE SYSTEM

Start the generator engine at least once every seven days and let it run at least 20 minutes. See “Weekly Exercise Cycle”.

‹INSPECT COOLING SYSTEM

Inspect engine cooling system. See “Maintenance Schedule”.

Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.

Check hose clamps for tightness.

‹CHECK ENGINE COOLANT LEVEL

See “Checking Fluid Levels”.

‹BATTERY FLUID

Check battery electrolyte fluid based on the Maintenance Schedule. Fluid should cover separa- tors in all battery cells. If fluid level is low, add dis- tilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.

‹ENGINE COOLANT

Check coolant level in coolant recovery bottle. See Specifications.

Add recommended coolant mixture as necessary.

Periodically remove radiator pressure cap (only when engine has cooled down) to make sure the coolant recovery system is functioning properly. Coolant should be at bottom of radiator filler neck. If coolant level is low, inspect gasket in radiator pressure cap. Replace cap, if necessary. To have pressure cap tested, contact an Authorized Service Dealer. Inspect cooling system and coolant recov- ery system for leaks.

MAINTENANCE OWNER/

OPERATOR CAN PERFORM

‹CHECK ENGINE OIL LEVEL

Refer to “Checking Fluid Levels”.

‹CHECK BATTERY

See “Checking Fluid Levels”.

Check battery cables for condition, tightness, cor- rosion or damage. Clean, tighten or replace as necessary.

‹PERFORM VISUAL INSPECTION

Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.

‹INSPECT EXHAUST SYSTEM

Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.

‹CHECK FAN BELT

Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt.

Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 of an inch. Adjust belt tension as required.

‹INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

DANGER

Do not attempt to adjust the governor. Only qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incor- rect frequency and/or voltage. Only qualified service technicians should adjust the governed speed.

04/06

0 .Rev Maint012

10-2

Image 17
Contents New standard of reliability Standby Generator Sets Table of Contents  Warning   Electrical Hazards  ‹ HOW to Obtain Service ‹ Operation and MaintenanceAuthorized Service Dealer Location Introduction‹ Data Label Identification RecordCoolant Recommendations Equipment DescriptionEngine OIL Recommendations Engine Protective Devices ‹ Fuel Requirements Fuel System‹ Natural GAS Fuel System ‹ LP Fuel SystemSpecifications ‹ Cold Weather KIT ‹ Reconfiguring the Fuel System‹ FOUR-LEAD, SINGLE-PHASE Stator Alternator Power Winding Connections‹ 3-PHASE Alternators Generator AC Lead ConnectionsInitial Inspection for QT Genset Startup InstallationPreparation Before START-UP ‹ START-UP Inspection START-UP Checklist‹ Preparation for START-UP Generator Control Operation Operating Unit with Manual Transfer Switch‹ Engine START-UP and Transfer ‹ Retransfer and ShutdownChecking Fluid Levels Cooling SystemMaintenance Owner Operator can Perform ‹ Spark Plugs ‹ Changing the Engine AIR Cleaner ‹ Coolant Change‹ Changing Engine OIL ‹ Cleaning the Generator Miscellaneous Maintenance‹ Battery ‹ Battery MaintenanceKW 150 KW Standby GAS Engine Driven Generator Sets Service ScheduleMaintenance Level 11-3 11-4 Problem Cause Correction Troubleshooting GuideStandby Generator Sets Page PAN CB Conn BOX Page UL Circuit Breaker QJ-2P Page Instr Hypot Test not Shown Page Components Included in 0F9696E Page Components Included in 0G1290E Page Weldment Frame 2.4L C2 Page Battery Tray C1 CPL Page Gasket Bosch 32 Page Engine 2.4L G2 Rework Page Weldment Radiator Support 2.4L Page Flange Fuel Inlet Page Rear Wrap C2 CPL Page Bracket Muffler Page Page Page Page Page Page Page Page Page Page Page C2 Units Standby Generator Sets Warranty

005261-1, 005262-1 specifications

Generac Power Systems, a leader in backup power solutions, offers a range of generators designed to meet different power needs. Among their notable products are the Generac models 005261-1 and 005262-1, which are both excellent options for residential and commercial applications. These generators are specifically designed to provide reliable power during outages, ensuring that homes and businesses remain operational when it matters most.

One of the standout features of the Generac 005261-1 and 005262-1 models is their automatic transfer switch technology. This feature allows the generators to detect power outages automatically and switch on within seconds, providing uninterrupted power. The systems are designed for ease of use, with a user-friendly control panel that displays critical information about the generator’s status and maintenance requirements.

Both models are powered by Generac's innovative engine technology, which ensures superior performance and fuel efficiency. The engines are engineered to run quietly while delivering ample power output. The 005261-1 typically offers up to 22 kW of backup power, while the 005262-1 goes up to 26 kW, making them suitable for larger homes or essential commercial applications.

In terms of construction, the Generac models feature durable weather-resistant enclosures, ensuring they can withstand harsh environmental conditions. Their compact design makes installation straightforward, with options for both concrete pads and low-profile installations. Furthermore, both generators are equipped with a state-of-the-art digital controller that allows users to monitor the system remotely.

Another important characteristic is the Generac Power Zone Mobile Link, which allows users to monitor their generator’s status via a smartphone app. This feature provides peace of mind, as users can receive alerts regarding power outages, routine maintenance, and operational status in real time, even when they are not home.

The maintenance of these generators is simplified by their built-in features, including an integrated maintenance reminder system that alerts users when service is due. This proactive approach aids in extending the life of the generator and optimizing performance over time.

In summary, the Generac Power Systems models 005261-1 and 005262-1 offer a blend of reliability, efficiency, and advanced technology. With automatic transfer switches, robust engine design, and smart monitoring capabilities, these generators stand out in the market as excellent choices for backup power needs. Whether for residential use or light commercial applications, users can trust in Generac’s commitment to delivering dependable power solutions.