Wiring Instructions
Control Voltage Wiring
1.A knockout is also provided in the back of the unit for control wiring. This knockout is sized for 1/2" conduit. (see Figure 13)
2.Thermostat wire shall be as follows:
a.Line voltage control models: Use NEC Class 1, 600V, 90˚C, AWG #10 wire with copper conductor or same gauge wire as supply line.
b.24 volt control models (B package): Use NEC Class 1, 600V, 90˚C, AWG #18 wire with copper conductor.
Use H1 + P1, terminals for connection (Do not use jumpers).
3. Install wall thermostats in accordance with the installation instructions supplied with the thermostat.
NOTE: Do not locate thermostat in an area exposed to unusual temperature conditions or poor air circulation.
NOTE: a. Line voltage control models of 3.3KW and 5.0KW ratings that are 208 and 240 volt, wired for
be used with a wall thermostat. This applies to the following models: | |||
|
|
|
|
These models come factory wired for single phase. When these models are converted in the field to
b.When using model number
4.Connect the thermostat wires to terminals H1 and P1 as shown in Figure 13. On 208 and 240 volt,
BACK | FRONT | Figure 14. |
Manual reset limit
| Heater Elements |
| A manual reset thermal limit is |
| ||
|
|
|
| Line Voltage | factory installed on all models. | FRONT |
|
|
|
| Control Models | The limit is located on the front of |
|
To Thermostat | H1 | H2 | F2 | (Singe Phase): | the heater. The manual reset limit |
|
Install jumpers |
| |||||
|
|
|
| will not reset until the button is |
| |
|
|
|
| between H1 and H2 | pushed and heater has cooled |
|
| P1 | P2 | F1 | and P1 and P2 on | down. (208/240V line voltage con- | Manual Reset Limit |
|
| 208/240V units | trol heaters use two manual reset | |||
Connect Thermostat | Control Terminal Board | (note dashed lines). |
| |||
limits) |
| |||||
Wires To P1 and H1 |
|
| ||||
|
|
|
|
|
|
Figure 13. Thermostat wiring connections