3M manual Instructions, 3M Cold Shrink QS-IIISplicing Kit 5797A-MT, 78-8126-0432-6-A

Models: 5797A-MT 78-8126-0432-6-A

1 12
Download 12 pages 57.13 Kb
Page 1
Image 1
Cold Shrink QS-III

Cold Shrink QS-III

Three-Conductor Splice Kit for use on Armor and Non-Armor Cables

Instructions

IEEE Std. 404 35 kV Class 250 kV BIL

Cable Range Requirements
Kit Number
Cable Insulation
Conductor

 

O.D. Range

Size Range

 

 

 

5797A-MT
1.07" to 1.70"1/0 AWG - 350 kcmil*

 

(27,2 mm to 43,2 mm)(60 - 185 mm2)

 

 

 

*Splices (including size transitions) can be made to smaller or larger conductors, provided both cables are within the Insulation O.D. Range and the connector meets the dimensional requirements shown below.

Connector Dimensional Requirements

 

Minimum

Maximum

 

inches (mm)

inches (mm)

 

 

 

Outside Diameter

0.51" (13,0 mm)

1.70" (43,2 mm)

 

 

 

Length

 

 

Aluminum (Al/Cu)

------

6.00" (152 mm)

 

 

 

Length

 

 

Copper (Cu)

------

6.50" (165 mm)

 

 

 

3MCold Shrink

QS-III Splicing Kit

5797A-MT

78-8126-0432-6-A

CAUTION

Working around energized high-voltage systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling high-voltage electrical equipment. De-energize and ground all electrical systems before installing product.