3M 78-8126-0432-6-A, 5797A-MT manual 4.0Install Splice, mm measured from the CENTER of connectors

Models: 5797A-MT 78-8126-0432-6-A

1 12
Download 12 pages 57.13 Kb
Page 6
Image 6
4.0Install Splice

4.0Install Splice

4.1Install connectors. See Table on front cover of

this instruction for proper connector dimensions. Crimp connectors per recommendations from connector manufacturer. For standard 3Mconnectors, refer to the table at the end of this instruction for crimping information.

4.2Apply a tape marker to core semi-con insulation screens of Cable Y (cable side which does not contain splice body) at a distance of 10"

(254 mm) measured from the CENTER of connectors.

4.3Position cold shrink copper connector adapter over CENTER of connector. Shrink the adapter near center of connector by pulling and unwinding the loose core ribbon end in a counter-clockwise direction.

4.4Remove any excess oxidation inhibitor from connector ends if aluminum connectors are used.

Clean cable using standard practice:

a.Do not use solvent or abrasive on cable semi-conductive insulation shield.

b.If abrasive is used on cable insulation, do not reduce diameter below the 1.07" (27,2 mm) minimum specified for the splice.

10" (254 mm)

78-8126-0432-6-A

6

Page 6
Image 6
3M 78-8126-0432-6-A, 5797A-MT manual 4.0Install Splice, mm measured from the CENTER of connectors