TWO
CAUTION
TO PREVENT CONDENSATION THE MINIMUM BOILER INLET TEMPERATURE IS 100°F (38°C)
30
SEE PAGE 31 FOR ADDITIONAL PIPING INFORMATION.
IMPORTANT
THE INSTALLATION OF SAFETY FLOW SWITCHES AS SHOWN IS REQUIRED TO PROTECT THE BOILER IN CASE OF WATER SERVICE INTERRUPTION OR CIRCULATOR FAILURE.
NOTE: THERMOMETERS, RELIEF VALVES, CIRCULATORS, SAFETY FLOW SWITCHES AND TANK CONTROLS ARE AVAILABLE THROUGH A.O.SMITH.
CAUTION
PUMP MUST BE RATED FOR SYSTEM OPERATING TEMPERATURE AND PRESSURE.
*SAFETY RELIEF VALVE RATING SHOULD NOT EXCEED PRESSURE CAPACITY OF ANY COMPONENT IN THE SYSTEM.
INSTALL IN ACCORDANCE WITH ALL LOCAL CODES.
+BALL VALVES ARE SHOWN FOR SERVICING BOILER, HOWEVER, LOCAL CODES SHALL GOVERN THEIR USAGE.
ALL PIPING MUST BE SUPPORTED.
Guide To Pipe and Pump Sizing
Two (2) Boiler Systems
| Common |
|
| Manifold Pipe | Boiler Pipe Size |
Model | Size "A" (Min.) | "B" (Min.) and Pump |
720, 840 |
| |
| NPT | See Table 7 |
3" |
| |
| NPT |
|
Pipe and pump capacities for two (2) boiler systems based on 100 equivalent feet (30 meters) heater to tank loop.
FIGURE 23