It is the aim of the T.R.S. to prevent flue gasses from the water heater entering the room where the water heater has been placed, instead of passing through the flue to outside atmosphere. The
After the cause of the reentry of flue gasses has been traced the device can be put back into operation again. In case of T.R.S. the RESET button has to be pressed first.
If this failure occurs frequently, this indicates that the flue suffers from down draught conditions. We advice that necessary remedial actions be carried out by a competent person.
Important
If the water heater is put out of operation by a failure, this may be caused by the T.R.S.. If there is a RESET button on the thermostat this is visible because the button rose. The device can be put back into operation by pressing the
The T.R.S. should never be put out of operation. Reentry of flue gasses to the building could be harmful and cause poisoning or death.
Attention:
Instruction addition for installer.
Fitting the Thermal Reflux Safeguard:
1.Remove the two screws from the lid;
2.Position the support (with pre- assembled TRS) onto the lid;
3.Secure the support, using both screws;
4.Interconnect the male and female connectors on the lid.