8.Take the end of the tube at the bottom of the floor and route it to a suitable drain. This will provide an area where the condensate can drain without affecting the area around the appliance.

9.Once installed along with the rest of the vent configuration, make sure to operate the unit through at least one heat up cycle to ensure there is no leakage around the hose barb or any joints of the VAA or vent pipe system.

FIGURE 23: Typical Horizontal Installation

Installation for VAA with 3 & 4 inch Pipe for Vertical Vent

Some applications may require the use of 3 or 4 inch vent pipe for longer vent lengths. Please refer to the Figure 24 as you review these instructions. Refer back to the vertical VAA installation steps but with the following changes to the vent construction.

3 inch vent (Vertical VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The installer must use 2 inch vent pipe between the blower assembly and the inlet into the VAA. On the outlet side of the VAA, a short run of 2 inch vent pipe is required. Each of the short pieces of 2 inch pipe entering and exiting the VAA must not exceed 6 inches (15 cm) in length. From this point on, a 2 inch to 3 inch adapter may be used. From the 2 inch to 3 inch adapter, the installer may use up to 65 equivalent feet (19.8 m) of pipe, see Figure 24 for typical installation.

4 inch vent (Vertical VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The installer must use 2 inch vent pipe between the blower assembly and the inlet into the VAA. On the outlet side of the VAA, a short run of 2 inch vent pipe is required. Each of the short pieces of 2 inch pipe entering and exiting the VAA must not exceed 6 inches (15 cm) in length. From this point on, a 2 inch to 4 inch adapter may be used. From the 2 inch to 4 inch adapter, the installer may use up to 128 equivalent feet (39.0 m) of pipe, see Figure 24 for typical installation.

Remember to operate the unit for at least one heat cycle to ensure there are no air leaks in the vent joints of the VAA and the vent pipe system. Air leaks will allow flue gas by-products to disseminate into the room creating an unsafe environment and could cause illness, asphyxiation and/or even death.

FIGURE 24: Typical Installation for Vertical Vent with 3 or 4 inch Pipe

Installation of VAA with 3 & 4 inch Pipe for Horizontal Vent

Some applications may require the use of 3 or 4 inch vent pipe for longer vent lengths. Please refer to the Figure 25 as you review these instructions. Refer back to the horizontal VAA installation steps but with the following changes to the vent construction.

3 inch vent (Horizontal VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The installer must use 2 inch vent pipe between the blower assembly and the inlet into the VAA. On the outlet side of the VAA, a short run of 2 inch vent pipe is required. From this point on, a 2 inch to 3 inch adapter may be used. From the 2 inch to 3 inch adapter, the installer may use up to 52 equivalent feet (15.8 m) of pipe. This is 8 equivalent feet (2.4

m)less than the original 60 equivalent feet (18.3 m) specified with one elbow due to the 2 inch elbow instead of a 3 inch elbow required for the vent from the blower to the inlet of the VAA, see Figure 25 for typical installation.

4 inch vent (Horizontal VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The installer must use 2 inch vent pipe between the blower assembly and the inlet into the VAA. On the outlet side of the VAA a short run of 2 inch vent pipe is required. From this point on, a 2 inch to 4 inch adapter may be used. From the 2 inch to 4 inch adapter, the installer may use up to 102 equivalent feet (31.1 m) of pipe. This is 18 equivalent feet (5.5 m) less than the original 120 equivalent feet (36.6 m) specified with one elbow due to the 2 inch elbow instead of a 4 inch elbow required for the vent from the blower to the inlet of the VAA, see Figure 25 for typical installation.

Remember to operate the unit for at least one heat cycle to ensure there are no air leaks in the vent joints of the VAA and the vent pipe system. Air leaks will allow flue gas by-products to disseminate into the room creating an unsafe environment and could cause illness, asphyxiation and/or even death.

FIGURE 25: Typical Installation for Horizontal Vent with 3 or 4 inch

23

Page 23
Image 23
A.O. Smith W/HOT instruction manual Inch vent Vertical VAA Installations, Inch vent Horizontal VAA Installations

W/HOT specifications

A.O. Smith, a leading manufacturer of water heating solutions, has made its mark in the industry with innovative products that combine efficiency, reliability, and advanced technology. Among its standout offerings is the A.O. Smith W/HOT series, designed to meet the diverse needs of residential and commercial customers.

The W/HOT series showcases a variety of tankless water heaters characterized by their ability to provide endless hot water on demand. Unlike traditional tank water heaters, which can run out of hot water during heavy usage, the W/HOT series ensures a constant supply, making it an ideal choice for families and businesses with high hot water needs. This feature not only enhances convenience but also optimizes energy usage by eliminating the standby heat loss associated with storage tanks.

One of the key technologies integrated into the W/HOT series is the microprocessor control system. This intelligent technology allows the unit to monitor water usage patterns and adjust operation accordingly. By optimizing heating cycles based on actual demand, this feature helps improve energy efficiency, resulting in lower utility bills without compromising performance.

The W/HOT series also incorporates advanced heat exchanger technology, enabling rapid heating of water as it passes through the system. This means minimal wait time for hot water and reduced energy consumption, as the unit only heats water when it is needed. The heat exchangers are designed for durability and effective heat transfer, helping to extend the overall lifespan of the unit.

Safety is a top priority in the design of A.O. Smith water heaters. The W/HOT series is equipped with multiple safety features, including a built-in thermal shut-off switch and safety sensors that prevent overheating. Additionally, the units are designed to comply with industry standards and regulations, ensuring peace of mind for users.

Installation flexibility is another defining characteristic of the W/HOT series. These tankless water heaters can be installed in various locations, requiring minimal space compared to traditional units. Their compact design makes them suitable for tight spaces, such as closets or utility rooms.

Overall, the A.O. Smith W/HOT series represents a commitment to innovation and quality in water heating solutions. Its combination of tankless design, advanced technology, and safety features makes it an excellent choice for those seeking efficient and reliable hot water access. Whether for residential or commercial use, A.O. Smith continues to lead the way in delivering top-tier water heating solutions that meet the evolving needs of consumers.