ADTRAN OPTI-3 Battery Backup Operation, Cable for the MX2800, Battery Backup Units, Mounting

Models: MX2810 OPTI-3

1 6
Download 6 pages 27.87 Kb
Page 4
Image 4
Figure 3. Cable for the MX2800

P/N 1200657L2) that has a molded modular connector on one end and four soldered wire tips on the other (see Figure 3).

“ground wire” in a customer equipment room. 18 AWG or larger ground wire is recommended.

Figure 3. Cable for the MX2800

Connect the soldered ends of the wires to the modular con- nector that fits into the chosen power bus using a small slotted screwdriver. (The power buses are labeled A and B on the rear of the chassis.) Use the following wiring conventions (holding the connector as it will be inserted in the chassis):

Left

WHITE

Battery Backup Alarm Wire

 

 

 

 

RED

Negative Terminal Wire

 

 

 

 

BLACK

Positive (RET) Wire

 

 

 

Right

GREEN

Ground Terminal Wire

 

 

 

Secure the ends of the wires and plug the connector into the chassis on the desired power bus (A or B). Connect the other end to the DC wiring harness of the PSU wiring harness and plug the AC plug into the AC power source.

Battery Backup Units

Mounting

When using the PS/BC in conjunction with available ADTRAN Battery Backup Units (BBUs), one of the following mounting options should be used:

Wallmounting the PS/BC (refer to Wallmounting on page 2).

Mounting the PS/BC to the product chassis containing the DC power supply.

Mounting the PS/C to the BBU.

Refer to your specific ADTRAN product system documentation to determine the optimal mounting solution for your system.

GROUNDING INSTRUCTIONS

For complete details on product grounding requirements, re- fer to the Network Turnup Procedure in your product System Manual.

GR-1089-CORE Requirement

An equipment grounding conductor that is not smaller in size than the ungrounded branch-circuit supply conductor is to be installed as part of the circuit that supplies the product or system.

The ground connector on the PS/BC provides an additional ground reference (the third prong of the AC plug is also grounded) and may be connected to the “ground bus” or

4. BATTERY BACKUP OPERATION

The following information is applicable when using the PS/BC with any available ADTRAN BBU.

Alarm and Battery Disconnect Relays

Two relays support Power Supply operation:

Alarm relay

Battery disconnect relay

Alarm Relay and Alarm Signal

The Alarm relay is provided for customer use. In normal op- eration the contact alarm relay is open. If an AC power failure occurs and the unit defaults to the battery backup, the relay will cycle open.closed once per second (that is one second open then one second closed). The tolerance on this cycle time is 25 percent.

This indicates the battery is discharging in support of the load. If battery voltage decreases to 45 V the relay stays closed to indicate the battery is becoming depleted. The relay will open automatically when normal AC voltage is restored. Table 3 summarizes the alarm relay operation.

Table 3. Alarm Relay Operation

Condition

Alarm Relay

 

 

 

 

Normal

Open

 

 

AC Power Failure/Battery

Cycles open/closed

Backup engaged

once per second

 

 

Battery voltage is less than

Stays closed

40V

 

 

 

An alarm signal that cycles synchronously with the alarm relay is provided on the output cable. This signal, which is open during normal operation, cycles between open and ground during battery backup (as described for the alarm relay), and is ground when the battery voltage falls below 45V.

Battery Fail Alarm

For battery backup systems that employ the optional Battery Test Assembly an alarm signal is provided to the PS/BC that indicates a failed battery (in need of immediate replacement). This signal is passed to the Alarm Relay and Output Alarm Signal. When a failed battery is detected, it is indicated by the Alarm Relay cycling open for 450 ms, then closed for 450 ms. Battery failure is also indicated by the output alarm signal cycling open to ground at the same rate.

Battery Disconnect Relay

The battery disconnect relay disconnects the battery pack from the system if the battery voltage falls below 40 VDC. This feature prevents damage tot he batteries. The batteries

4

Issue 1, January 2004

61175043L3-5A

Page 4
Image 4
ADTRAN OPTI-3, NIU3 Battery Backup Operation, Cable for the MX2800, Battery Backup Units, Grounding Instructions, Mounting