Alarm 30:
This message appears when a parallel system has a UPS shutdown due to high voltage.
Alarm 31:
When an over temperature is detected by the PFC or inverter temperature sensors, after 1 minute time the inverter will be turned off automatically.
If over temperature condition remains after another 1 minute with the rectifier working, rectifier is also blocked (alarm 60).
Alarm 32:
When the rectifier is overloaded, depending on the level of this overload, the inverter will be shut down after some time according to the rectifier overload curve and this alarm will appear. If this overload is still present with the inverter switched off, the rectifier will be blocked after 30 seconds and blocking alarm 61 will appear.
Alarm 33:
This message appears when an internal error in the digital signal processor (*) DSP in the AC rectifier module occurs. The inverter will shut down immediately. Four attempts will be made to restart the UPS, then the inverter will be blocked.
Alarm 34:
This alarm appears when an output
Alarm 35:
With the inverter is running, if there’s a bypass phase rotation error, the inverter will shut down.
Alarm 36:
This alarm appears when there is a (*) DSP Internal Error in the UPS module, shutting down the UPS immediately. There will be 2 more retries before the UPS blocking.
Alarm 37:
This alarm describes that on battery mode, the battery bank reaches the 10.5 V/battery pack This is the end of backup time, shutting down the UPS.