LOCATION OF NAME PLATE

file:///D:/System/DATA/Dx/ds1/Us/iss1/EINS512426/EINS512426.htm

Fig. 4 - Model GC3 Open Flue DESN 512430

LOCATION OF NAME PLATE

The model and serial numbers for this appliance are found on the data plate. These numbers must be used when requesting advice from your Aga Distributor. The name plate is located on the burner housing panel behind top left door. The maximum gas inlet pressure at the appliance must not exceed 12 inches w.g. (2.98kPa) for Natural Gas and 14 inches w.g. (3.48kPa) for L.P. Gas. The minimum gas inlet pressure at the appliance must be 4 inches w.g. (1kPa) Natural Gas and 10 inches w.g. (2.248kPa) L. P. Gas to enable the correct manifold pressure to be obtained.

INITIAL LIGHTING OF RANGE

In a cold range, difficulty may be experienced in maintaining the main burner alight on initial light-uponly. Should this occur, set

the control knob to theINITIAL LIGHTING OF RANGEposition. Depress knob and light pilot. With the pilot flame established, rotate the gas valve control knob 2 anti-clockwise to its low fire position where upon the main burner will automatically light. Leave in the low fire position for at least 30 minutes. After 30 minutes rotate the control knob further anti-clockwise to the mid position in the green band for normal running.