The AC drive provides overload protection for the drive motor. However, a separate three- phase circuit breaker or
Note: Do NOT use fuses in place of a circuit breaker.
CAUTION
Do not use a phase adder on any variable- speed machine.
SW037
The
The connection should be shielded in a liquid- tight or approved flexible conduit with proper conductors of correct size installed in accordance with the National Electric Code or other applicable codes. The connection must be made by a qualified electrician using the wiring diagram provided with the washer- extractor, or according to accepted European standards for
Installation
Use wire sizes indicated in the Electrical Specifications chart for runs up to 50 feet. Use next larger size for runs of 50 to 100 feet. Use 2 sizes larger for runs greater than
100 feet.
For personal safety and for proper operation, the
If a delta supply system is used, the high leg may be connected to L3 on the cabinet freestanding models as all machines are equipped with control transformers.
Note: Timers or similar devices that could switch off the machine automatically are not to be installed, whether in the machine’s supply circuit or elsewhere.