Programming

 

Table 2 (Continued)

 

 

Pause 5 seconds, then Reverse

Display shows ‘rEv’

wash speed – 60 seconds, pause

 

Outputs: Motor operates wash speed reverse; drain closed

several seconds before entering

 

drain (next step)

 

 

 

Drain (cannot advance to spin

For 2 speed models: Display flashes “drAI”/“For” (keypad RINSE LED on)

here)

For variable-speed models: Display flashes “drAI”/“For” while operating in low speed

 

forward; then flashes “drAI”/“dISt” while operating at distribution speed.

 

If balance fails, repeats the “drAI”/“For” then “drAI”/“dISt” sequence above and balance

 

indicator is on during “drAI”/“For” message (rebalance attempt). Tries up to 10 times in

 

TEST cycle, then aborts test cycle.

 

 

 

Outputs: Drain closed for first part of step (less than 20 seconds), then drain off.

 

2 speed models: Wash speed forward

 

Variable-speed: Forward during “drAI”/“For”; distribution during “drAI”/“dISt”.

 

 

Spin: 3 minutes

For 2 speed models: display shows “SPIn” (keypad SPIN LED on)

 

For variable-speed models: display shows “HI 1” (keypad SPIN LED on)

 

 

 

Outputs: Spin (low spin for variable-speed – refer to motor chart below)

 

 

Highest Spin speed (variable-

For 2 speed models: this step is skipped, goes to coast (the next step)

speed models ONLY):

For variable-speed models: display shows “HI 2” (keypad SPIN LED on)

2 minutes

 

Outputs: Highest spin speed selected (refer to motor chart below)

 

 

 

Coast

Displays “SdLY” (spin delay coast)

 

 

 

Outputs: All off

 

 

Stop routine

Display shows “01” (1 minute remaining). Agitates briefly then unlocks the door, shows

 

“doNE” while sounding the buzzer 10 seconds; “doNE” shows until door is opened

 

(DOOR LED on while showing “doNE”, meaning “door ready to open”).

 

 

NOTE: ON appears ONLY where motor control outputs are on (otherwise they are off). Outputs referenced are on control unit fuse board. Outputs are as labeled on the fuse board.

Motor Speed Chart

 

2 Speed Motor Outputs

 

 

 

 

 

Fwd

Rev

Spin

 

 

 

 

Motor off (no rotation)

 

 

 

 

 

 

 

Wash speed forward

ON

 

 

 

 

 

 

Wash speed reverse

 

ON

 

 

 

 

 

Distribution (variable-speed ONLY)

NA

NA

NA

 

 

 

 

Spin (low spin speed “HI 1” for variable-speed)

 

 

ON

 

 

 

 

Highest spin (“HI 2” – variable-speed ONLY)

NA

NA

NA

 

 

 

 

NA – Not Applicable

F232168