Allied Telesis AT-PWR01 Only trained and qualified personnel should connect a DC power supply

Models: AT-PWR01

1 9
Download 9 pages 3.93 Kb
Page 6
Image 6
For AC Models:

6

AT-PWR01 & AT-PWR01-80

8.Apply power to the PSU

For AC Models:

Read the AT-PWR01 Safety and Statutory Information booklet before connecting a PSU to an external AC power source. A copy of the safety booklet is included with each PSU.

Plug the provided AC power cord into the AC power inlet on the rear panel of the PSU and connect the PSU to the mains power supply.

Important information for service personnel only:

CAUTION: double pole/neutral fusing

The ratings of fuses FH101 and FH102 is 250 V, 5 A

For DC models:

Read the AT-PWR01 Safety and Statutory Information booklet before connecting a PSU to a DC power source. A copy of the safety booklet is included with each PSU.

Only trained and qualified personnel should connect a DC power supply.

For centralized DC power connection, the switch should be installed only in Restricted Access Areas (Dedicated Equipment Rooms, Equipment Closets, or the like) in accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NAPA 70.

DC supply cable specifications:

Three core cable is required

Minimum core size: 3.3 mm2 (12 AWG) high strand count copper wire

Minimum cable rating: 600 V, 90 degrees Celsius

DC power supply specifications:

40 to 60 V, 48 V nominal

Supports either positive grounded or negative grounded operation Circuit protection:

10 Amp certified/Listed circuit breaker is required for branch circuit protection

To connect the DC supply:

Ensure that the supply cable is not live.

1.Remove the transparent protective terminal cover.

2.Strip the supply cable wires to expose 7.5mm (0.31 in.) of bare conductor. Terminate with JST FN5.5-5 or equivalent, using a crimp tool.

3.Connect the ground wire to the ground terminal. Terminals can be identified by the diagram on the switch’s rear panel. Tighten the terminal to between 2.4 and 4.0 Nm (21.3 and 35.4 lbf in).

C613-04049-01 REV B

Page 6
Image 6
Allied Telesis AT-PWR01 manual Only trained and qualified personnel should connect a DC power supply, For AC Models