A.1 Fatal Error Messages

Fatal error messages indicate the application is suspending due to either an invalid critical configuration parameter, or a critical process initialization sequence failed.

F001: Unable to locate table <table_name>

Cause:

The DCA was unable to locate one of its required configuration tables.

Remedy:

Ensure the <table_name> table exists and is comprised of at least one record.

F002: A197_SRU rec <x>, duplicate SRU address <y>

Cause:

Two SRUs mapped by the same record in A197_COM table have the same SRU address.

Remedy:

Make sure all records in the A197_SRU table that are mapped byt the same communication port have different addresses.

F003: A197_SRU rec <x>, SRU used for multiple COM recs

Cause:

Record <x> in the A197_SRU table is mapped by more than one communication port.

Remedy:

Make sure that no records in the A197_SRU table are mapped by the same communication port.

F004: COM rec <x>, Interchar Timeout must be less than Rx Time

Cause:

The RX Message Timeout in record <x> of the A197_COM table is less than the Inter Char Timeout.

Remedy:

Make sure the Interchar Timeout is less than the RX Message Timeout.