A.1 Fatal Error Messages
Fatal error messages indicate the application is suspending due to either an invalid critical configuration parameter, or a critical process initialization sequence failed.
F001: Unable to locate table <table_name>
Cause:
•The DCA was unable to locate one of its required configuration tables.
Remedy:
•Ensure the <table_name> table exists and is comprised of at least one record.
F002: A197_SRU rec <x>, duplicate SRU address <y>
Cause:
•Two SRUs mapped by the same record in A197_COM table have the same SRU address.
Remedy:
•Make sure all records in the A197_SRU table that are mapped byt the same communication port have different addresses.
F003: A197_SRU rec <x>, SRU used for multiple COM recs
Cause:
•Record <x> in the A197_SRU table is mapped by more than one communication port.
Remedy:
•Make sure that no records in the A197_SRU table are mapped by the same communication port.
F004: COM rec <x>, Interchar Timeout must be less than Rx Time
Cause:
•The RX Message Timeout in record <x> of the A197_COM table is less than the Inter Char Timeout.
Remedy:
•Make sure the Interchar Timeout is less than the RX Message Timeout.