Chapter 5: Configuring the Partition Definition Table (A197_PAR)

The A197_PAR table contains one record for each data partition defined for each SRU. A data partition is a continuous range of X3.28 word addresses that contain sub-system data. The range of records for a particular SRU is specified in configuration table A197_SRU by the First Partition and Number of Partitions parameters. Each SRU can have more than one of each type of partition.

Name

 

Range

 

 

Description

 

 

 

 

 

 

 

 

Data Type

 

Digital Input

 

 

This parameter specifies the type of data that the partition will

 

 

 

Analog Input

 

 

contain. Digital Input partitions require 16 digital input system

 

 

 

 

 

points per word. Analog Input partitions require one analog input

 

 

 

 

 

 

 

 

 

 

 

 

system point per word.

 

 

 

 

 

 

Start Address

0 .. 32767

 

This parameter specifies the word address of the first word in the

 

 

 

 

 

 

partition. Each partition must have a range of addresses that is

 

 

 

 

 

 

unique to all other partitions mapped by the same SRU record. In

 

 

 

 

 

 

other words, partitions that are mapped by the same SRU record

 

 

 

 

 

 

should not have ranges that overlap.

 

 

 

 

 

 

Number of Words

1 .. 32767

 

This parameter specifies the number of 16-bit words in this

 

 

 

 

 

 

partition. Note that Analog Input partitions require an even number

 

 

 

 

 

 

of words.

 

 

 

 

 

 

For Digital Input partitions, each word requires 16 digital input

 

 

 

 

 

 

system points.

 

 

 

 

 

 

For Analog Input partitions, each SRU analog input point value

 

 

 

 

 

 

requires two words and each word requires 1 analog input system

 

 

 

 

 

 

point.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 6 Partition Definition Table Parameters

Restricted

A197-0CG-1.00-2

Full

11

 

Page 21
Image 21
GE X3.28 manual Configuring the Partition Definition Table A197PAR, Partition Definition Table Parameters