F005: A197_PAR rec <x> and <y>, Partitions overlap

Cause:

Records <x> and <y> of the A197_PAR are mapped by the same SRU record and have ranges of addresses that overlap.

Remedy:

Make sure all partitions that are mapped by the same SRU have address ranges that do not overlap.

F006: A197_COM rec <x>, Only one SRU allowed in Full-Duplex

Cause:

When in Full-Duplex mode, only one SRU should be mapped.

Remedy:

Make sure there is only one SRU mapped for A197_COM records that are configured for Full-Duplex mode.

F100: Future expansion points not NULLPTR

Cause:

There is an interface error between the DCA and the DCA engine.

The DCA stack is not valid.

Remedy:

Contact the Customer Service Department and report this error.

Reboot the RTU.

F101: Unable to find table <table_name>

Cause:

The DCA was unable to locate one of its required configuration tables.

Remedy:

Ensure the <table_name> table exists and is comprised of at least one record.