Amana 7M11TA, 5M11TA Electrical Requirements, Safety Features, i i WARNING, Compressor Lockout

Models: 18M23TB 7M11TA 5M11TB 5M11TA

1 8
Download 8 pages 61.95 Kb
Page 2
Image 2
Electrical Requirements

Electrical Requirements

Electrical Grounding Instructions

This appliance is equipped with a three-pro ng grounding plug fer protection against possible shock hazards. Ifatwe-prong wall receptacle is encountered, the customer is required to contact a qualified electrician and have the two-prong wall receptacle replaced with a properly grounded three-prong

wall receptacle in accordance with the National Electrical Code.

Room air conditioners are designed to operate according to requirements on the nameplate and as shown in Table 1. Fuse or circuit breaker ratings must be according to the fuse instruction label and as shown in Table 1. Do not plug models marked "Use on Single Outlet Circuit Only" into a circuit with another appliance or light fixture.

i _i WARNING

To avoid death, personal injury or property damage due to electrical shock, this unit

must be grounded. Do not under any

circumstances cut or remove the round

grounding prong from the plug. Do not use a two-prong adapter.

WARNING

To avoid death, personal inju ry or property damage due to electrical shock, do not use an extension cord. Do not pinch the power cord. Do not remove the warning tag from the power cord.

Unit Plug

Type

Receptacle

Circuit

Rating,

Voltage

Rating

 

 

Required

Breaker or

On Unit Nameplate

 

 

 

Time

 

 

 

 

 

Delay

Fuse

 

 

(_

 

 

125V-15AMP

115V

NEMA No

5-15P NEMA No 5=15R

 

 

 

 

 

 

 

250V-15AMP

230/208V rated

 

 

 

at 12 amperes or less

 

 

 

 

 

NEMA No 6-15P

NEMA No 6-15R

 

 

 

 

 

 

 

 

 

230/208V

rated over

 

 

 

250V-20AMP

12 amperes

but not more

NEMA No 6-20P

NEMA No 6-20R

 

 

than 16 ampf_res

 

 

 

 

 

 

 

250V=30AMP

230/208V rated

 

 

 

at 24 amperes or Eess

 

 

 

 

 

NEMA No 6-30P

NEMA No 6-30R

 

 

 

 

Table 1

Safety Features

This room air conditioner is equipped with an electronic control to improve comfort and ensure reliability.

Compressor Lockout

To extend the life of the compressor a three minute time delay will occur when:

Electrical power is first supplied to the unit

The thermostat is turned down immediately after the compressor stops running,

The Fan Control is quickly turned from FAN ONLY to COOLING mode or vice versa.

Low Voltage Protection

This unit is equipped with "brownout" protection. In case of an extreme brownout, the Amana control will interrupt power to the unit to prevent compressor failure. When the line voltage reaches at least 100 VAC, the control will re- energize your unit.

Note: A compressor lockout will occur after the unit is re- energized.

,Digital Temperature Setting

-Temperature can be set from 60°F to 90°F in I°F increments

,Digital Temperature Display

-Shows indoor room temperature in FAN ONLY mode

-Shows desired temperature setting in other modes ,Computer Memory that Remembers

-The unit remembers the last settings used when last turned on.

,TempAsure ® Thermostat

- Maintains set temperature within 1.5°F for maxi- mum comfort

,Smart Cool

,Energy Saver with TempAsure ® air sampling

,Delay Timer

2

Page 2
Image 2
Amana 7M11TA Electrical Requirements, Safety Features, i i WARNING, must be grounded. Do not under any, Compressor Lockout