I. Unit Specifications
MODEL | PGC24B0452A | PGC24B0702A | PGC30B0702A | PGC36B0702A | PGC36B0902A |
Cooling Capacity Btuh | 24,000 | 24,000 | 30,000 | 36,000 | 36,000 |
SEER | 12.50 | 12.50 | 12.30 | 12.00 | 12.00 |
Heating |
|
|
|
|
|
Input Btuh | 45,000 | 70,000 | 70,000 | 70,000 | 90,000 |
Output Btuh | 35,000 | 55,000 | 55,000 | 55,000 | 70,000 |
AFUE | 80.9 | 80.1 | 80.1 | 80.1 | 80.4 |
Temperature Rise °F | |||||
Number of Burners | 2 | 3 | 3 | 3 | 4 |
Compressor |
|
|
|
|
|
R.L. Amps | 12.9 | 12.9 | 15 | 20 | 20 |
L.R. Amps | 62.5 | 62.5 | 76 | 90.5 | 90.5 |
Condenser Coil |
|
|
|
|
|
Face Area (sq. ft.) | 12.3 | 12.3 | 12.3 | 14 | 14 |
Rows Deep | 1 1/2 | 1 1/2 | 2 | 2 | 2 |
Fins/Inch | 13 | 13 | 13 | 13 | 13 |
Condenser Fan |
|
|
|
|
|
Diameter (in.) | 20 | 20 | 20 | 20 | 20 |
CFM | 2670 | 2670 | 2700 | 3060 | 3060 |
Condenser Fan Motor |
|
|
|
|
|
Horsepower | 1/8 | 1/8 | 1/4 | 1/4 | 1/4 |
R.L. Amps | 0.8 | 0.8 | 1.2 | 1.5 | 1.5 |
L.R. Amps | 1.5 | 1.5 | 3 | 3.4 | 3.4 |
Blower Motor |
|
|
|
|
|
Horsepower | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
R.L. Amps | 4.3 | 4.3 | 4.3 | 4.3 | 4.3 |
L.R. Amps |
| Protected by redundant electronic control circuits |
| ||
Blower Wheel Dia. x Width (in.) | 10x7 | 10x7 | 10x7 | 10x7 | 10x7 |
Rated CFM, Cooling | 850 | 850 | 1100 | 1300 | 1300 |
Max. External | 0.8" wc | 0.8" wc | 0.8" wc | 0.8" wc | 0.8" wc |
Combustion Blower |
|
|
|
|
|
Diameter x Width (in.) | 4 x 1.25 | 4 x 1.25 | 4 x 1.25 | 4 x 1.25 | 4 x 1.25 |
No. | 1 | 1 | 1 | 1 | 1 |
Condenser Blower Motor |
|
|
|
|
|
H.P. | 0.03125 | 0.03125 | 0.03125 | 0.03125 | 0.03125 |
F.L. Amps. | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
Press. Switch Setting (" W.C.) | |||||
Ignition - Lockout Timing (sec.) | 4 | 4 | 4 | 4 | 4 |
Flame Sense Current (microamps) |
|
|
|
|
|
Minimum | 1 | 1 | 1 | 1 | 1 |
Maximum | 6 | 6 | 6 | 6 | 6 |
Evaporator Coil |
|
|
|
|
|
Face Area (Sq. Ft.) | 4 | 4 | 4 | 4 | 4 |
Rows Deep | 2 | 2 | 2 | 4 | 4 |
Fins/Inch | 16 | 16 | 16 | 12 | 12 |
External Filter Size (Sq. Ft.) | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 |
Drain Line Size (in.) | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 |
Expansion Device (Cooling) | Capillary | Capillary | Capillary | Capillary | Capillary |
Refrigerant Charge |
| Refer to unit name plate for correct charge |
| ||
Power Supply** | |||||
Min. Circuit Ampacity | 21.3 | 21.3 | 24.3 | 30.8 | 30.8 |
Max. Overcurrent Device | 30 | 30 | 35 | 45 | 45 |
Electrical Entrance Size |
|
|
|
|
|
Power Supply | 1 1/4", 1 1/2", 2" | 1 1/4", 1 1/2", 2" | 1 1/4", 1 1/2", 2" | 1 1/4", 1 1/2", 2" | 1 1/4", 1 1/2", 2" |
Low Voltage | 7/8" | 7/8" | 7/8" | 7/8" | 7/8" |
Approx. Shipping Weight (lb.) | 385 | 394 | 418 | 437 | 443 |
1)United States Installation
2)Specification subject to change without notice. See sales specification sheets for certain BTUH capacities.
3)This PGC series complies with requirements embodied in the American National Standard
4)Filters are not supplied with units, but filters must be installed in the unit filter rack or in the return air system.
**While the above data is presented as a guide, it is important to electrically connect the unit and properly size overcurrent protection and wires in accordance with the National Electrical Code and all existing local codes.
Operating tolerance: Minus 5% on 208 VAC, Plus 10% on 208 VAC and 230 VAC, Minus 10% on 230 VAC
Table 1A