Amana PGC(24-60)B, PGB58B installation instructions Unit Specifications, Gas Pack Specifications

Models: PGB58B PGC(24-60)B

1 33
Download 33 pages 11.48 Kb
Page 2
Image 2

I. Unit Specifications

MODEL

PGC24B0452A

PGC24B0702A

PGC30B0702A

PGC36B0702A

PGC36B0902A

Cooling Capacity Btuh

24,000

24,000

30,000

36,000

36,000

SEER

12.50

12.50

12.30

12.00

12.00

Heating

 

 

 

 

 

Input Btuh

45,000

70,000

70,000

70,000

90,000

Output Btuh

35,000

55,000

55,000

55,000

70,000

AFUE

80.9

80.1

80.1

80.1

80.4

Temperature Rise °F

20-50

30-60

30-60

30-60

40-70

Number of Burners

2

3

3

3

4

Compressor

 

 

 

 

 

R.L. Amps

12.9

12.9

15

20

20

L.R. Amps

62.5

62.5

76

90.5

90.5

Condenser Coil

 

 

 

 

 

Face Area (sq. ft.)

12.3

12.3

12.3

14

14

Rows Deep

1 1/2

1 1/2

2

2

2

Fins/Inch

13

13

13

13

13

Condenser Fan

 

 

 

 

 

Diameter (in.)

20

20

20

20

20

CFM

2670

2670

2700

3060

3060

Condenser Fan Motor

 

 

 

 

 

Horsepower

1/8

1/8

1/4

1/4

1/4

R.L. Amps

0.8

0.8

1.2

1.5

1.5

L.R. Amps

1.5

1.5

3

3.4

3.4

Blower Motor

 

 

 

 

 

Horsepower

0.5

0.5

0.5

0.5

0.5

R.L. Amps

4.3

4.3

4.3

4.3

4.3

L.R. Amps

 

Protected by redundant electronic control circuits

 

Blower Wheel Dia. x Width (in.)

10x7

10x7

10x7

10x7

10x7

Rated CFM, Cooling

850

850

1100

1300

1300

Max. External

0.8" wc

0.8" wc

0.8" wc

0.8" wc

0.8" wc

Combustion Blower

 

 

 

 

 

Diameter x Width (in.)

4 x 1.25

4 x 1.25

4 x 1.25

4 x 1.25

4 x 1.25

No.

1

1

1

1

1

Condenser Blower Motor

 

 

 

 

 

H.P.

0.03125

0.03125

0.03125

0.03125

0.03125

F.L. Amps.

0.5

0.5

0.5

0.5

0.5

Press. Switch Setting (" W.C.)

-0.65

-0.65

-0.65

-0.65

-0.65

Ignition - Lockout Timing (sec.)

4

4

4

4

4

Flame Sense Current (microamps)

 

 

 

 

 

Minimum

1

1

1

1

1

Maximum

6

6

6

6

6

Evaporator Coil

 

 

 

 

 

Face Area (Sq. Ft.)

4

4

4

4

4

Rows Deep

2

2

2

4

4

Fins/Inch

16

16

16

12

12

External Filter Size (Sq. Ft.)

3.6

3.6

3.6

3.6

3.6

Drain Line Size (in.)

3/4

3/4

3/4

3/4

3/4

Expansion Device (Cooling)

Capillary

Capillary

Capillary

Capillary

Capillary

Refrigerant Charge

 

Refer to unit name plate for correct charge

 

Power Supply**

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

Min. Circuit Ampacity

21.3

21.3

24.3

30.8

30.8

Max. Overcurrent Device

30

30

35

45

45

Electrical Entrance Size

 

 

 

 

 

Power Supply

1 1/4", 1 1/2", 2"

1 1/4", 1 1/2", 2"

1 1/4", 1 1/2", 2"

1 1/4", 1 1/2", 2"

1 1/4", 1 1/2", 2"

Low Voltage

7/8"

7/8"

7/8"

7/8"

7/8"

Approx. Shipping Weight (lb.)

385

394

418

437

443

1)United States Installation

2)Specification subject to change without notice. See sales specification sheets for certain BTUH capacities.

3)This PGC series complies with requirements embodied in the American National Standard ANSI-Z21.47 Central Furnaces.

4)Filters are not supplied with units, but filters must be installed in the unit filter rack or in the return air system.

**While the above data is presented as a guide, it is important to electrically connect the unit and properly size overcurrent protection and wires in accordance with the National Electrical Code and all existing local codes.

Operating tolerance: Minus 5% on 208 VAC, Plus 10% on 208 VAC and 230 VAC, Minus 10% on 230 VAC

Table 1A

Gas Pack Specifications

2

Page 2
Image 2
Amana PGC(24-60)B, PGB58B installation instructions Unit Specifications, Gas Pack Specifications