American Aldes HRV 1500 SFD Ducting - General, Drains, The Ductwork System, Consult local Codes

Models: HRV 1500 SFD 1500 SFDE

1 16
Download 16 pages 34.16 Kb
Page 11
Image 11
Ducting - General

Ducting - General

Drains

Connect the drain pans in the bottom of the HRV to a drain line fastened to the holes provided. Create a “P” trap to prevent odors from being drawn through. Make sure the drain line slopes down to drain properly and if this is not possible a condensate pump will be required for removal of the water. Note that stagnant water is a leading cause of indoor air quality problems; confirm drainage after installa- tion by pouring water into trays. Drain line must be installed where it will not freeze.

The Ductwork System

A well designed ducting system will allow the HRV to oper- ate at its maximum efficiency. Avoid the use of undersized ducting and sharp radius bends and tees which can signifi- cantly increase the system pressure drop and reduce the air flows.

NOTE: Fully insulated ducting with an integral vapor bar- rier must be used on all runs passing through un- heated areas in order to avoid condensation prob- lems and energy losses from the air streams.

* Consult local Codes

To minimize pressure drop and noise, galvanized metal ducts sized for 1200 fpm (6.09 m/s) (maximum velocity) are recommended. Keep ducting as short as possible and use a minimum of elbows and tees. Connecting sections and shorter runs may be flexible ducting one size larger than the metal duct. Use flexible duct connectors at the HRV to avoid noise transmission. All duct joints must be secured with screws, rivets or duct sealant and sealed with aluminum duct tape to prevent leakage.

Outside Weatherhoods

The HRV 1500 SFDE is shipped with 2 weatherhoods inside the cabinet which attach to the outer ends of the cabinet using bolts provided. The HRV 1500 SFD requires exterior hoods to be provided by the contractor.

NOTE: It is extremely important to design and install the fresh air intake in an area where the hoods will gather the freshest air, free from restriction.

Recommended:

No less than 10 ft. (3 m) apart from each other, or per local code restriction.

At least 18 in. (46 cm) above ground level.

Away from sources of contaminants, such as automobile exhaust fumes, gas meters, garbage containers, cooling towers, etc.

Not exposed to prevailing winds, whenever reasonably possible.

The outside perimeter of the weatherhood must be caulked to prevent leakage into the building. The design and size of the weatherhoods or louvers chosen by the installer must allow for adequate free area. Water and snow penetration of the system is minimized when the airflow does not ex- ceed 750 FPM (3.81m/s) free area velocity.

Ducting from the Weatherhoods

Galvanized sheet metal ducting with sufficient cross sec- tion with an integral single piece vapor barrier should be used to connect the HRV to the weatherhoods. All ducting must meet ULC Class 1 Fire Rating. A minimum R value of insulation should be equal to 4 (RSI 0.75), or as stated in local codes. A good bead of high quality caulking (prefer- ably acoustical sealant) and taping with a high quality alu- minum foil tape is recommended to seal the duct to both the HRV and the weatherhood.

Warmside Ducting - General

Ducting from the HRV to different areas within the building should be galvanized metal whenever possible. To mini- mize airflow losses in the ductwork system, all ducts should be as short as possible and with as few bends or elbows as possible. 45° elbows are preferred to 90° elbows, when- ever possible. Use Y tees instead of 90° tees whenever possible. All duct joints must be fastened securely and wrapped with a quality duct tape to prevent leakage. We recommend aluminum foil tape.

11

Page 11
Image 11
American Aldes HRV 1500 SFD Ducting - General, Drains, The Ductwork System, Consult local Codes, Outside Weatherhoods