The Integrated HVAC System

The Integrated HVAC System

WARNING: This unit is a quiet, efficient, low pres- sure system. Special care and attention should be given if connecting this unit to any other air han- dler that may draw more air than this unit is de- signed to accommodate.

In installations where it is satisfactory to provide general exhaust from the space, the air to be exhausted may be- taken directly from the return air plenum to the HRV as it is drawn back to the air handler. Fresh air supplied by the HRV is then introduced directly into the return air plenum

but at a location closer to the air handler. The air handler would have a constant running blower to effectively distrib- ute the fresh air and remove the stale air. Balancing damp- ers would be located in both the HRV supply and exhaust ducts between the return air plenum and the HRV.

In installations where it is necessary or desirable to have an extended ducting system, it is recommended to have a qualified designer/engineer size and design the ducting system to ensure optimum removal and distribution of air is achieved.

Electrical Connections

System is 208/240V, 1 phase, 60 Hz. This unit meets all local codes and requirements.

It is STRONGLY recommended that an electrical discon- nect be installed prior to the HRV, and that it is turned off and locked out before servicing the unit.

All electrical connections should be made by a qualified electrician.

Two (2) knockouts are provided. One is to be used for line voltage, and the other one for 24V control wires.

Balancing

The HRV 1500 SFD/SFDE have been programmed to provide constant airflow on each airstream for external static pres- sures of up to 1” w.g.

Within this range, each airflow can be adjusted as described on page 5. After 1” w.g. of external static pressure, the unit acts as a regular system and the following balancing pro- cedure should be used.