AD-20

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

NOTES: A. When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.

B.Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.

C.Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.

 

SERVICE

 

WIRE

APPROX.

CIRCUIT

 

PHASE

AMP DRAW

 

VOLTAGE

SERVICE

BREAKER

Gas

 

60 Hz

50 Hz

 

 

 

 

120

2

10.9

---

15

 

240

3

 

6

15

 

 

 

 

 

 

 

 

240

3

5.8

---

15

 

 

 

 

 

 

 

 

240

3

---

28.5

35

Electric

 

 

 

 

 

 

240

3

28.3

---

35

 

416

4

---

18

25

 

 

 

 

 

 

 

IMPORTANT: Figures shown are for non-reversing models ONLY.

IMPORTANT: The wire size must be properly sized to handle the related current.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or obligation.

19

Page 23
Image 23
American Dryer Corp AD-20 installation manual Electrical Service Specifications PER Dryer