SINGLE DRYER VENTING

IMPORTANT: For exhaust duct runs over 30 feet a minimum size of 10 inches must be used.

HORIZONTAL VENTING

When horizontal single 8-inch venting is used, the duct work to the outlet cannot exceed 30 feet (refer to Illus. A below). This calculation of 30 feet compensates or allows for the use of a maximum of only one (1) elbow (which is the outside outlet protection).

Illus. A

13

Page 17
Image 17
American Dryer Corp MDG-50 installation manual Single Dryer Venting