American Dryer Corp ML-130 III Electrical Information, Gas And Steam, Electrical Requirements

Models: ML-130 III ML-130DR

1 28
Download 28 pages 36.88 Kb
Page 14
Image 14
ML-130DR Multiple Dryer Venting

IMPORTANT: Minimum duct size for a dryer is 12-inches (30.48 cm) for a round duct and 10-3/4” x 10-3/4” (27.31 cm x 27.31 cm) for a square duct. The duct size must not be reduced anywhere down stream of the dryer.

Exhaust back pressure measured by a manometer at each tumbler exhaust duct area should not exceed 0.6” WC (1.48 mb).

14-INCHES (35.56 CM) DIAMETER

2,150 CFM (60.88 CMM) EXHAUST CONNECTION AT COMMON DUCT

ML-130DR Multiple Dryer Venting

Electrical Information ________________

Electrical Requirements

It is your responsibility to have all electrical connections made by a properly licensed and competent electrician to ensure that the electrical installation is adequate and conforms to local and state regulations or codes. In the absence of such codes, all electrical connections, material, and workmanship must conform to the applicable requirements of the National Electrical Code ANSI/NFPA NO. 70-LATEST EDITION or in Canada, the Canadian Installation Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION.

IMPORTANT: Failure to comply with these codes or ordinances, and/or the requirements stipulated in this manual can result in personal injury or component failure.

NOTE: Component failure due to improper installation will void the warranty.

Each dryer should be connected to an independently protected branch circuit. The dryer must be connected with copper wire only. Do not use aluminum wire, which would cause a fire hazard. The copper conductor wire/cable must be of proper ampacity and insulation in accordance with electric codes for making all service connections.

NOTE: The use of aluminum wire will void the warranty.

Wiring diagrams are affixed to the inside at the top front control door and to the rear upper back guard/panel.

Electrical Service Specifications

GAS AND STEAM

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES: A. When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.

B.Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.

C.Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.

SERVICE

 

WIRE

APPROX.

CIRCUIT

PHASE

AMP DRAW

VOLTAGE

SERVICE

BREAKER

 

 

 

60 Hz

50 Hz

 

208

3

14.5

20

240

3

14.6

20

230

3

17.4

25

380

3

8.5

15

380

4*

8.7

15

400

4*

8.7

15

416

4*

9.0

15

440

3

8.7

15

460

3

7.8

15

480

3

7.8

15

575

3

5.8

15

* 3-Wire is available.

 

 

 

7/31/08

IMPORTANT: The dryer must be connected to the electric supply shown on the data label. In the case of 208 VAC or 230/240 VAC, the supply voltage must match the electric service specifications of the data label exactly.

! WARNING

208 VAC and 230/240 VAC are not the same. Any damage done to dryer components due to improper voltage connections will automatically void the warranty.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or obligation.

14

American Dryer Corp.

113335 - 12

Page 14
Image 14
American Dryer Corp ML-130 III installation manual Electrical Information, Gas And Steam, ML-130DR Multiple Dryer Venting