1.The dryer must be installed on a sound level floor capable of supporting its weight. Carpeting must be removed from the floor area that the dryer is to rest on.
IMPORTANT: “The dryer must be installed on noncombustible floors only.”
2.The dryer must not be installed or stored in an area where it will be exposed to water or weather.
3.The dryer is for use in noncombustible locations.
4.Provisions for adequate air supply must be provided as noted in this manual (refer to Fresh Air Supply Requirements in Section D).
5.Clearance provisions must be made from noncombustible construction as noted in this manual (refer to Dryer Enclosure Requirements in Section C).
Even though a
6.Provisions must be made for adequate clearances for servicing and for operation as noted in this manual (refer to Dryer Enclosure Requirements in Section C).
7.Dryer must be exhausted to the outdoors in an area where correct exhaust venting can be achieved as noted in this manual (refer to Exhaust Requirements in Section E).
IMPORTANT: Dryer must be installed in a location/environment, which the ambient temperature remains between 40° F (4.44° C) and 130° F (54.44° C).