| Technical Specifications | |
|
|
|
| Type | Description |
|
|
|
|
|
|
| Power input | Transformer class 2, IN 120 VAC; OUT 16 VAC, 75 VA |
|
|
|
| Battery | 12 VDC, 7 Ah battery supervised, provides up to 12 hours of operation |
|
|
|
| Operating Temperatures | From 2°C to 49°C (35°F to 120°F) indoor use only |
|
|
|
| Humidity Level | 0 to 85% (relative humidity |
|
|
|
| Cabinet Dimensions | 37.59 cm (14.8 in) x 30.48 cm (12.0 in) x 12.57 cm (4.95 in) |
|
| |
|
|
|
| Cabinet Weight | 4.0 kg (8.82 lb) |
|
|
|
| PCB dimension | 22.86 cm (9 in) X 13.97 cm (5.5 in) X 5.20 cm (2.04 in) |
|
|
|
| Reader types | Wiegand, proximity, ABA Clock and Data, bar code, magnetic, integrated keypad, |
|
| smartcard and others |
|
|
|
| Reader power output | 12 VDC and 5 VDC @ 175 mA max each, protected and supervised |
|
|
|
| Monitored points (inputs) | 16 monitored points, single EOL (End of Line), double EOL, without EOL and |
|
| 1 |
|
|
|
| Points maximum wiring | AWG #22 - 600 m (2,000 ft) |
|
|
|
| Door strike power | 12 VDC, 250 mA max for |
|
|
|
| Reader outputs | 16 outputs, 25mA max each, open collector outputs |
|
|
|
| Auxiliary outputs | LEDs (LED, OUT1 and OUT2) and buzzer (Buz) for each individual door, 25mA max each, |
|
| open collector outputs |
|
|
|
| Relay controlled output | 4 onboard Form C Relay controlled outputs, 30 VDC, 3 Amps max each |
|
|
|
| Communication ports | 1 x |
|
|
|
| Expansion port | 1 x SPI |
|
| max shared with 12 VDC Auxiliary port |
|
|
|
| Auxiliary port | 1 x Auxiliary 12 VDC, 500 mA maximum shared with SPI expansion port |
|
|
|
| Communication speed | - Up to 115200 Bauds (automatic detection) over |
|
| - 10/100 Mb/s BaseT over Ethernet |
|
|
|
| Flash memory | 16 MB for application storage |
|
|
|
| RAM memory | 64 MB for application loading and running, protected by a |
|
| minimum of 75 hours |
|
|
|
| Network autonomy | Distributed data and processing |
|
|
|
| Certifications / Listing | EN55022, |
|
| FCC: Class A |
|
| UL 294, UL 1076 |
|
|
|
| 15 |