American Dynamics KT-MOD-INP16 Terminal Connections, Configurations with Jumpers, Applying Power

Models: KT-MOD-INP16

1 3
Download 3 pages 26.18 Kb
Page 2
Image 2

KT-MOD-INP16

KT-400 Expansion Module 16-Zone Input with SPI Cable Install Sheet

4.Configurations with Jumpers

There are 3 jumpers available to configure the KT-MOD-INP16. The jumper settings apply to ALL 16 inputs at the same time.

Note: Jumper JP4 is for future use.

DRY (without end-of-line resistor): In a simple NC dry contact configuration, the secure state is given when a short is detected. The voltage becomes lower than the Level 1 threshold value (1.1V).

The alarm state is given when the input is open. The voltage becomes higher than the Level 2 threshold value (3.75V). If the alarm switch is programmed as NO device, the alarm state will be given when the input is shorted.

EOL (with end-of-line resistor): For NC device, the secure state is given when a single resistor is detected. The voltage becomes lower than the Level 3 threshold value (2.9V) and higher than the Level 2 threshold value (2.25V).

The alarm state is given when the input is open or short. The voltage becomes higher than the Level 4 threshold value (3.75V) or lowers than the Level 1 threshold value (1.1V). If the alarm switch is programmed as NO device, the alarm state will be given when a single resistor is detected.

5.Applying Power

After all wiring is completed, connect the 16 VAC to the KT-400. Connect the battery leads to the battery, and then apply power to the AC transformer.

Note: Do not connect power until all wiring is complete.

Terminal Connections

Module no.: ______________________________________________________________________________________

Date of installation: _______________________________________________________________________________

KT-400 Name: ____________________________________________________________________________________

KT-400 SITE NAME: _______________________________________________________________________________

KT-400 Serial Number: _____________________________________________________________________________

AUX: ___________________________________________________________________________________________

SPI BUS (FROM): _________________________________________________________________________________

SPI BUS (TO): ____________________________________________________________________________________

Z1:

 

Z9: __________________________________________

Z2:

 

Z10: _________________________________________

Z3:

 

Z11: _________________________________________

Z4:

 

Z12: _________________________________________

Z5:

 

Z13: _________________________________________

Z6:

 

Z14: _________________________________________

Z7:

 

Z15: _________________________________________

Z8:

 

Z16: _________________________________________

Tel.: 1 (450) 444 2030 • Toll Free: 1-888-222-1560 • Fax: 1 (450) 444 2029 • Internet: www.kantech.com

DN1776-0809

Copyright © 2008 Tyco International Ltd. and its Respective Companies. All Rights Reserved. • Specifications may change without notice.

Kantech and the Kantech logo are trademarks of Tyco International Ltd. and its Respective Companies.

Page 2
Image 2
American Dynamics KT-MOD-INP16 specifications Terminal Connections, Configurations with Jumpers, Applying Power