American Power Conversion 100 VAC user manual Some or all front panel indicators are flashing

Models: 100 VAC

1 25
Download 25 pages 59.17 Kb
Page 22
Image 22
None. The UPS will return to normal operation when the power is restored and the battery has a sufficient charge.

UPS is plugged into wall outlet and only the battery charge bar graph is lit.

• The UPS is shut down and the battery is discharged from an extended outage.

Replace battery light is lit and the UPS beeps for one minute every five hours.

• Weak batteries.Charge the batteries for 24 hours and perform self-test (see Self-Test, page 9) to see if it clears.

• Bad or expired battery.Replace the batteries. Refer to Replacing the Battery, page 15.

Replace battery light flashes, battery charge bar graph is off, and the UPS beeps continuously.

• Battery not connected properly.

Check that the battery connector is fully engaged.

Some or all front panel indicators are flashing.

Internal UPS fault or battery charger failure.

Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately.

With the warning interval setting shown above, the battery graph flashes, and the UPS operates normally when the battery capacity is insufficient to give the full warning time that the unit is set for. The table bellow shows all conditions that could be interpreted as “flashing”.

Condition

Display

Beeper

Low battery, load still powered (Q bit 6

One or more LEDs flashing on the battery

Continuous beeping

set)

capacity bar graph with either the on-line

(user settable)

 

LED or on battery LED on

 

Low battery shut down (8 bit 0 set, Q

Only battery capacity bar graph LEDs on

None

bit 6 set if flashing)

or flashing

 

Standby enable (~ bit 7 set, Q bit 6 set

Only battery capacity bar graph LEDs on

None

if flashing)

or flashing

 

Boost or trim relay fault (' bit 6 set)

Center 6 LEDs flashing in unison

None

Sleep, i.e., delayed wake up (8 bit 3

Center 6 LEDs (boost, overload, on-line,

None

set)

on battery, trim, replace battery) scrolling

 

 

down vertically (then back to top)

 

Shut down till power returns (8 bit 4

Center 6 LEDs (boost, overload, on-line,

None

set)

on battery, trim, replace battery) scrolling

 

 

up-down vertically

 

Battery overvoltage, i.e., charger

Center 6 LEDs flashing in unison with on-

Continuous beeping

failure (8 bit 5 set)

line, boost, trim, and/or on battery LEDs

 

 

staying on and with both bar graphs

 

 

functioning 'normally'

 

DC imbalance (' bit 4 set)

Left half of LEDs (power bar graph,

None

 

boost, on-line, trim) flashing in unison.

 

Battery disconnected (' bit 5 set)

Replace battery LED flashing and battery

Continuous beeping

 

capacity bar graph off; all other LEDs

 

 

unaffected

 

Output overvoltage (' bit 7 set)

Right half of LEDs (battery capacity bar

None

 

graph, overload, on battery, replace

 

 

battery) flashing in unison.

 

990-7096 Rev. 2

18

Page 22
Image 22
American Power Conversion 100 VAC user manual Some or all front panel indicators are flashing, Condition Display Beeper

100 VAC specifications

American Power Conversion (APC), a leading global provider of power management solutions, offers a range of products that cater to the evolving needs of consumers and businesses alike. Among its extensive product line, the APC 100 VAC model stands out as an essential component for maintaining reliable power for sensitive electronic equipment.

The APC 100 VAC is engineered to deliver stable voltage and reliable power to various devices, making it ideal for both residential and commercial environments. One of its core features is its capacity to regulate voltage levels, ensuring that sensitive equipment operates within specified parameters. This feature helps prevent damage caused by voltage fluctuations, which could otherwise lead to equipment failure or downtime.

Another distinguishing characteristic of the APC 100 VAC is its built-in surge protection. The unit is designed to guard connected devices against voltage spikes that occur due to lightning strikes or power outages. By diverting excess voltage away from sensitive components, the APC 100 VAC helps prolong equipment life and maintain operational efficiency.

In terms of technology, the APC 100 VAC is equipped with advanced monitoring capabilities. Users can easily track power usage, voltage levels, and overall system performance through an intuitive user interface. This technology not only aids in proactive maintenance but also empowers users to optimize their power consumption, leading to cost savings over time.

Moreover, the APC 100 VAC features a compact and sleek design, which allows it to fit seamlessly into various spaces without causing clutter. Its lightweight structure makes installation and portability hassle-free, catering to users who may need to relocate their devices frequently.

Additionally, the model integrates a variety of connectivity options, including USB and serial ports, enabling it to connect with different types of devices for enhanced functionality. This versatility makes the APC 100 VAC valuable for a range of applications, from home offices to data centers.

In summary, the American Power Conversion 100 VAC model is a robust solution for managing power needs. Its voltage regulation, surge protection, advanced monitoring technology, compact design, and connectivity options establish it as a standout choice for those seeking enhanced power management. Whether for personal or commercial use, the APC 100 VAC is poised to deliver unparalleled reliability and performance.