8
NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE
OR OPTIONAL SMART SLOT ACCESSORY CARDS.
FUNCTION FACTORY
DEFAULT
USER SELECTABLE
CHOICES DESCRIPTION
Low Battery Warn-
ing
2 minutes
PowerChute soft-
ware provides
automatic, unat-
tended shutdown
when approxi-
mately 2 minutes
of battery oper-
ated runtime re-
mains.
: Brightly illu-
minated - low bat-
tery warning level of
about 2 minutes.
: Dimly illumi-
nated - low battery
warning level of
about 5 minutes.
: No illumina-
tion; low battery
warning level is
approximately 8
minutes.
The UPS will beep when 2 minutes of
battery runtime remains.
Change the warning interval setting by
pressing the voltage sensitivity button,
while pressing and holding the
button.
Change the low battery warning inter-
val setting to the time that the operat-
ing system or system software requires
to safely shut down.
Synchronized
Turn-on Delay
0 seconds 0, 60, 120, 180, 240,
300, 360, 420 sec-
onds
Specify the time the UPS will wait
after the return of utility power before
turn-on, (to avoid branch circuit over-
load).
High Transfer
Point
100 V model:
108 Vac
120 V model:
127 Vac
208 V model:
225 Vac
230 V model:
253 Vac
100 V model:
108, 110, 112,
114 Vac
120 V model:
127, 130, 133,
136 Vac
208 V model:
225, 229, 233,
237 Vac
230 V model:
253, 257, 261,
265 Vac
Set the high transfer point higher to
avoid unnecessary battery usage when
the utility voltage is usually high and
the connected equipment is specified
to operate with input voltages this
high.
Low Transfer Point 100 V model:
92 Vac
120 V model:
106 Vac
208 V model:
182 Vac
230 V model:
208 Vac
100V model:
92, 90, 88, 86 Vac
120 V model:
97, 100, 103,
106 Vac
208 V model:
170, 174, 178,
182 Vac
230 V model:
196, 200, 204,
208 Vac
Set the low transfer point lower when
the utility voltage is usually low and
the connected equipment is specified
to operate with input voltages this low.
Output Voltage
230 V Model Only
230 Vac 220, 230, 240 Vac Select the output voltage.