12
On-Battery Run Time
Note:
UPS battery life differs based on usage and environment.
APC recommends that the battery/batteries be changed once every two years.
Typical On-Battery Run Time Versus Load, in Hours
Load (VA) Run Time (hours)
100 7.17
150 5.95
200 5.04
300 3.88
400 2.96
500 2.37
600 1.92
800 1.40
1000 1.06
1200 0.83
1400 0.65
1600 0.54
2000 0.39
2200 0.33
2500 0.26
3000 0.19
3500 0.16
4000 0.13
4500 0.11
5000 0.09