Storage

Storage Conditions

Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at least two hours. Remove any accessories in the accessory slot and disconnect any cables connected to the computer interface port to avoid unnecessarily draining the battery.

Extended storage

At -15 to +30 °C (+5 to +86 °F), charge the UPS’s battery every six months.

At +30 to +45 °C (+86 to +113 °F), charge the UPS’s battery every three months.

User Configuration Items

Note: Setting these items requires optional software or hardware.

Function

Factory

User Selectable

Description

 

Default

Choices

 

Automatic Self-Test

Every 14

Every 7 days (168

Sets the interval at which the UPS will

 

days (336

hours), On Startup

execute a self-test.

 

hours)

Only, No Self-Test

 

UPS ID

UPS_IDEN

Up to eight characters

Use this field to uniquely identify the UPS

 

 

to define the UPS.

for network management purposes.

 

 

 

 

Date of Last Battery

Manufacture

Date of Battery

Reset this date on battery replacement.

Minimum Capacity Before

0 percent

15, 50, 90 percent

The UPS will charge its batteries to the

Return from Shutdown

 

 

 

specified percentage before return from a

 

 

 

 

shutdown.

Sensitivity

Normal

Reduced, Low

 

Set lower than normal sensitivity to avoid

 

 

 

 

lowered battery capacity and service life in

 

 

 

 

situations where the load can tolerate minor

 

 

 

 

power disturbances.

Duration of Low Battery

2 minutes

5, 7, 10 minutes

Sets the time before shutdown at which the

Warning

 

 

 

UPS issues a low battery warning. Set

 

 

 

 

higher than the default only if the OS needs

 

 

 

 

the time for graceful shutdown.

Alarm Delay After Line

5 second

30 second delay, At

To avoid alarms for minor power glitches,

Fail

delay

Low Battery

Al

set the alarm delay.

 

 

C di i

 

Shutdown Delay

20 seconds

180, 300, 600 seconds

Sets the interval between when the UPS

 

 

 

 

receives a shutdown command and when

 

 

 

 

shutdown occurs.

Synchronized Turn-on

0 seconds

60, 180, 300 seconds

To avoid branch circuit overload, the UPS

Delay

 

 

 

will wait the specified time after the return

 

 

 

 

of utility power before turn-on.

High Transfer Point

 

 

 

To avoid unnecessary battery usage, set the

200/208 Vac

229

224, 234, 239

 

High Transfer Point higher if the utility

230 Vac

253

264, 271, 280

 

voltage is chronically high and the load is

 

 

 

 

known to work well under this condition.

Low Transfer Point

 

 

 

Set the Low Transfer Point lower if the

200/208 Vac

177

168, 172, 182

 

utility voltage is chronically low and the

230 Vac

196

188, 204, 208

 

load can tolerate this condition.

 

 

 

 

 