10
Battery Charge and Run Times
Note:
UPS battery life differs based on usage and environment.
The tables below show both the time required for charging UPS and battery pack batteries for rated protection and typical
run times.
Note:
The SU5000UXI is designed for use with the UXBP48M or equivalent 48 Volt battery pack.
Typical Maximum Recharge Times (In Hours) To 90% Of Rated Capacity
Number of Battery Packs Recharge Time Number of Battery Packs Recharge Time
1 5 6 18
2 8 7 20.5
3 10.5 8 23
4 13 9 25.5
5 15.5 10 28
SU5000UXI Typical On-battery Run Times
Load VA With 1
battery pack
With 2
battery packs
With 3
battery packs
With 4
battery packs
With 5
battery packs
With 6
battery packs
1000 4.3 9.0 14.5 20.0 25.0 30.0
2000 2.1 4.8 7.5 9.9 12.5 15.0
3000 1.2 2.4 3.6 4.8 6.0 7.2
4000 0.5 1.4 2.3 3.2 4.0 4.8
5000 0.3 0.8 1.4 2.0 2.5 3.0