Battery Charge and Run Times

Note:

UPS battery life differs based on usage and environment.

The tables below show both the time required for charging UPS and battery pack batteries for rated protection and typical run times.

Note:

The SU5000UXI is designed for use with the UXBP48M or equivalent 48 Volt battery pack.

Typical Maximum Recharge Times (In Hours) To 90% Of Rated Capacity

Number of Battery Packs

Recharge Time

Number of Battery Packs

Recharge Time

1

5

6

18

 

 

 

 

2

8

7

20.5

 

 

 

 

3

10.5

8

23

 

 

 

 

4

13

9

25.5

 

 

 

 

5

15.5

10

28

 

 

 

 

SU5000UXI Typical On-battery Run Times

Load VA

With 1

With 2

With 3

With 4

With 5

With 6

 

battery pack

battery packs

battery packs

battery packs

battery packs

battery packs

 

 

 

 

 

 

 

1000

4.3

9.0

14.5

20.0

25.0

30.0

 

 

 

 

 

 

 

2000

2.1

4.8

7.5

9.9

12.5

15.0

 

 

 

 

 

 

 

3000

1.2

2.4

3.6

4.8

6.0

7.2

4000

0.5

1.4

2.3

3.2

4.0

4.8

 

 

 

 

 

 

 

5000

0.3

0.8

1.4

2.0

2.5

3.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 