Smart UPS Safety Guide

English

This Safety Guide contains important instructions that should be followed during installation and maintenance of the APC equipment and batteries. It is intended for APC customers who setup, install, relocate, or maintain APC equipment.

Handling Safety

Be careful. Do not lift heavy loads without assistance.

<18 kg (<40 lb.)

 

 

 

32-55 kg (70-120 lb.)

 

 

 

18-32 kg (40-70 lb.)

 

 

 

>55 kg (>120 lb.)

 

 

 

 

 

 

Equipment with casters is built to move on a smooth surface without any obstacles.

Do not use a ramp inclined at more than 10°.

This equipment is intended for installation in a temperature-controlled indoor area (0 to 40ΓC (+32 to +104ΓF)), free of conductive contaminants.

Electrical Safety

Do not work alone under hazardous conditions.

High short circuit current through conductive materials could cause severe burns.

A licensed electrician is required to install permanently wired equipment.

Check that the power cord(s), plug(s), and sockets are in good condition.

To reduce the risk of electric shock when grounding cannot be verified, disconnect the equipment from the AC power outlet before installing or connecting to other equipment. Reconnect the power cord only after all connections are made.

Do not handle any kind of metallic connector before the power has been removed.

Use one hand, whenever possible, to connect or disconnect signal cables to avoid a possible shock from touching two surfaces with different electrical grounds.

Connect the equipment to a three wire AC outlet (two poles plus ground). The receptacle must be connected to appropriate branch circuit/mains protection (fuse or circuit breaker). Connection to any other type of receptacle may result in a shock hazard.

CAUTION! Deenergizing Safety

If the equipment has an external battery pack connected, the output may be energized when the unit is not connected to an AC power outlet.

To deenergize pluggable equipment: first press the Off button for more than one second to switch the equipment off. Next disconnect the equipment from the AC power outlet. Finally, disconnect the battery.

To deenergize permanently wired equipment: set the power switch to standby . Next set the AC circuit breaker to standby . Then disconnect the batteries (including any expansion units). Finally, disconnect the AC power from the building power supply.

Pluggable equipment includes a protective earth conductor which carries the leakage current from the load devices (computer equipment). Total leakage current must not exceed 3.5 mA.

Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly effect its safety or effectiveness is not recommended.

WARNING! Battery Safety

This equipment contains potentially hazardous voltages. Do not attempt to disassemble the unit. Battery replacement using the procedures below is permissible. The unit contains no user serviceable parts. Repairs are performed only by factory trained service personnel.

Batteries must be recycled. Deliver the battery to an appropriate recycling facility or ship it to the supplier in the new battery’s packing material. See the new battery instructions for more information.

Do not dispose of batteries in a fire. The batteries may explode.

Do not open or mutilate batteries. They contain an electrolyte which is toxic and harmful to the skin and eyes.

To avoid personal injury due to energy hazard, remove wrist watches and jewelry such as rings when replacing the batteries. Use tools with insulated handles..

990-7082A REV4 7/01