Low Battery Warning.

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT

ACCESSORY CARDS.

FUNCTION

 

FACTORY

 

USER SELECTABLE

DESCRIPTION

 

DEFAULT

 

CHOICES

 

 

 

 

Low Battery Warning.

 

 

 

Brightly lit: Low battery

The low battery warning

 

 

 

PowerChute interface

 

 

 

warning interval is about

beeps are continuous when

 

 

 

 

 

 

two minutes.

two minutes of run time re-

software provides auto-

 

 

 

 

 

 

Dimly lit:

Low battery

main.

matic, unattended shut-

 

 

 

 

 

 

warning interval is about

 

down when approximately

 

 

 

You can change the warning

 

 

 

five minutes.

two minutes (by default) of

 

 

 

interval default setting

 

 

 

Off:

Low battery

battery operated run time

 

 

 

through PowerChute soft-

 

 

 

warning interval is about

remains.

 

 

 

ware.

 

 

 

eight minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Possible interval settings:

 

 

 

 

 

5, 7, 10, 12, 15, 18 min-

 

 

 

 

 

utes.

 

 

 

 

 

 

Synchronized Turn-on

0 seconds

20, 60, 120, 240, 480,

The UPS will wait the speci-

Delay

 

 

 

720, 960 seconds

fied time after the return of

 

 

 

 

 

 

 

 

utility power before turn-on

 

 

 

 

 

 

 

 

(to avoid branch circuit over-

 

 

 

 

 

 

 

 

load).

 

 

 

 

 

High Transfer Point

100V:

100V:

 

To avoid unnecessary battery

 

108VAC

110, 112, 114VAC

usage, set the high transfer

 

120V:

120V:

 

point higher if the utility volt-

 

 

age is chronically high and

 

127VAC

130, 133, 136VAC

the connected equipment is

 

230V:

230V:

 

known to work under this

 

 

condition.

 

253VAC

257, 261, 265VAC

 

 

 

 

 

 

 

Low Transfer Point

100V:

100V:

 

Set the low transfer point

 

92VAC

86, 88, 90VAC

lower if the utility voltage is

 

120V:

120V:

 

chronically low and the con-

 

 

nected equipment can tolerate

 

106VAC

97, 100, 103VAC

this condition.

 

230V:

230V:

 

 

 

208VAC

196, 200, 204VAC

 

 

 

 

 

 

 

 

 

 