3:USER CONFIGURABLE ITEMS

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT

ACCESSORY CARDS.

FUNCTION

 

FACTORY

 

USER SELECTABLE

DESCRIPTION

 

DEFAULT

 

CHOICES

 

 

 

 

 

 

Automatic Self-Test

 

Every 14 days

Every 7 days

This function sets the interval

 

(336 hours)

(168 hours),

at which the UPS will execute

 

 

 

 

On Startup Only, No

a self-test. Refer to your soft-

 

 

 

 

Self-Test

 

ware manual for details.

 

 

 

 

 

 

 

 

UPS ID

 

UPS_IDEN

 

Up to eight characters to

Use this field to uniquely

 

 

 

 

define the UPS

identify the UPS, (i.e. server

 

 

 

 

 

 

 

name or location) for network

 

 

 

 

 

 

 

management purposes.

 

 

 

 

 

 

 

 

Date of Last Battery Re-

Manufacture

Date of Battery Replace-

Reset this date when you

placement

Date

ment

 

replace the battery module.

 

 

 

 

mm/dd/yy

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Capacity Before

0 percent

15, 25, 35, 50, 60, 75, 90

The UPS will charge its bat-

Return from Shutdown

 

 

 

percent

 

teries to the specified percent-

 

 

 

 

 

 

 

age before return from a shut-

 

 

 

 

 

 

 

down.

 

 

 

 

 

 

 

 

Voltage Sensitivity

 

 

 

Brightly lit: UPS is set to

To change the UPS sensitiv-

 

 

 

The UPS detects and reacts

 

 

 

high sensitivity.

ity, press the voltage sensitiv-

 

 

 

 

 

 

Dimly lit:

 

ity button

 

(rear panel).

to line voltage distortions

 

 

 

UPS is set to

 

 

 

 

Use a pointed object (such as

by transferring to battery

 

 

 

medium sensitivity.

 

 

 

a pen) to do so.

operation to protect the

 

 

 

Off:

UPS is set to

 

 

 

 

 

 

connected equipment.

 

 

 

You can change the sensitiv-

 

 

 

low sensitivity.

Where power quality is

 

 

 

ity level through PowerChute

 

 

 

 

 

 

poor, the UPS may fre-

 

 

 

 

 

 

software.

 

 

quently transfer to battery

 

 

 

 

 

 

 

 

 

operation. If the connected

 

 

 

 

 

 

 

 

 

equipment can operate

 

 

 

 

 

 

 

 

 

normally under such condi-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tions, reduce the sensitivity

 

 

 

 

 

 

 

 

 

setting to conserve battery

 

 

 

 

 

 

 

 

 

capacity and service life.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Delay After Line

5 second delay

 

30 second delay, At Low

To avoid alarms for minor

Fail

 

 

 

Battery Condition, No

power glitches, set the alarm

 

 

 

 

 

 

 

delay.

 

 

 

 

 

 

 

Shutdown Delay

 

20 seconds

0, 60, 120, 240, 480, 720,

Sets the interval between the

 

 

 

 

960 seconds

time when the UPS receives a

 

 

 

 

 

 

 

shutdown command and ac-

 

 

 

 

 

 

 

tual shutdown.

 

 

 

 

 

 

 

 

 

 

7

Page 9
Image 9
American Power Conversion 750 VA user manual User Configurable Items