3:USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT
ACCESSORY CARDS.
FUNCTION |
| FACTORY |
| USER SELECTABLE | DESCRIPTION | ||||
| DEFAULT |
| CHOICES | ||||||
|
|
|
|
|
| ||||
Automatic |
| Every 14 days | Every 7 days | This function sets the interval | |||||
| (336 hours) | (168 hours), | at which the UPS will execute | ||||||
|
|
|
| On Startup Only, No | a | ||||
|
|
|
|
| ware manual for details. | ||||
|
|
|
|
|
|
|
| ||
UPS ID |
| UPS_IDEN |
| Up to eight characters to | Use this field to uniquely | ||||
|
|
|
| define the UPS | identify the UPS, (i.e. server | ||||
|
|
|
|
|
|
| name or location) for network | ||
|
|
|
|
|
|
| management purposes. | ||
|
|
|
|
|
|
|
| ||
Date of Last Battery Re- | Manufacture | Date of Battery Replace- | Reset this date when you | ||||||
placement | Date | ment |
| replace the battery module. | |||||
|
|
|
| mm/dd/yy |
|
|
|
| |
|
|
|
|
|
|
|
| ||
Minimum Capacity Before | 0 percent | 15, 25, 35, 50, 60, 75, 90 | The UPS will charge its bat- | ||||||
Return from Shutdown |
|
|
| percent |
| teries to the specified percent- | |||
|
|
|
|
|
|
| age before return from a shut- | ||
|
|
|
|
|
|
| down. |
|
|
|
|
|
|
|
| ||||
Voltage Sensitivity |
|
|
| Brightly lit: UPS is set to | To change the UPS sensitiv- | ||||
|
|
| |||||||
The UPS detects and reacts |
|
|
| high sensitivity. | ity, press the voltage sensitiv- | ||||
|
|
| |||||||
|
|
| Dimly lit: |
| ity button |
| (rear panel). | ||
to line voltage distortions |
|
|
| UPS is set to |
| ||||
|
|
| Use a pointed object (such as | ||||||
by transferring to battery |
|
|
| medium sensitivity. | |||||
|
|
| a pen) to do so. | ||||||
operation to protect the |
|
|
| Off: | UPS is set to | ||||
|
|
|
|
|
| ||||
connected equipment. |
|
|
| You can change the sensitiv- | |||||
|
|
| low sensitivity. | ||||||
Where power quality is |
|
|
| ity level through PowerChute | |||||
|
|
|
|
|
| ||||
poor, the UPS may fre- |
|
|
|
|
|
| software. |
|
|
quently transfer to battery |
|
|
|
|
|
|
|
|
|
operation. If the connected |
|
|
|
|
|
|
|
|
|
equipment can operate |
|
|
|
|
|
|
|
|
|
normally under such condi- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
tions, reduce the sensitivity |
|
|
|
|
|
|
|
|
|
setting to conserve battery |
|
|
|
|
|
|
|
|
|
capacity and service life. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Alarm Delay After Line | 5 second delay |
| 30 second delay, At Low | To avoid alarms for minor | |||||
Fail |
|
|
| Battery Condition, No | power glitches, set the alarm | ||||
|
|
|
|
|
|
| delay. |
|
|
|
|
|
|
| |||||
Shutdown Delay |
| 20 seconds | 0, 60, 120, 240, 480, 720, | Sets the interval between the | |||||
|
|
|
| 960 seconds | time when the UPS receives a | ||||
|
|
|
|
|
|
| shutdown command and ac- | ||
|
|
|
|
|
|
| tual shutdown. | ||
|
|
|
|
|
|
|
|
|
|
7