Lifebreath RNC155 manual Engineering Data - HRV, Model RNC200, Dimensions RNC200, Date, Contractor

Models: RNC155 RNC20 RNC95 RNC120D RNC10 RNC200 RNC5-TPD

1 36
Download 36 pages 54.76 Kb
Page 6
Image 6
Model RNC200

Engineering Data - HRV

Model RNC200

 

 

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE

The cross-flow heat recovery core transfers heat between the two air streams.

It is easily removed for cleaning or service.

MOTORS AND BLOWERS

Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation.

FILTERS

Washable air filters in exhaust and supply air streams.

MOUNTING THE HRV

Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.

DEFROST

Recirculating damper defrost system.

CASE

Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent

exterior condensation. Drain connections

two - 1/2" (12mm) OD.

WEIGHT 71 lbs. (32.5 kg)

SHIPPING WEIGHT 73 lbs. (33.5 kg)

CONTROLS - HRV System Control

HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV.

Standard LOW SPEED SETTING can be increased to medium low.

Off (Standby)/Low or OFF/HIGH speed operation is also available.

OPTIONAL MAIN CONTROLS (only one main control can be installed on the system)

99-116

Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH

 

Switch (3 wire) 20 gauge wire (min.) 100' length (max.)

99-2040

20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch.

 

The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low

 

speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire

 

(min.) 100' length (max.)

99-RECIRC

Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch.

 

The Recirculation Switch will toggle from continuous low speed ventilation to continuous

 

low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.)

99-130

Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length

 

(max.)

OPTIONAL TIMERS

99-132

20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge

 

wire (min.) 100’ length

99-104

Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3

 

wire) 20 gauge wire (min.) 100' length

99-101

60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire)

 

20 gauge wire (min.) 100' length (max.)

WARRANTY

Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.

Performance (HVI certified)

Net supply air flow in cfm (L/s) against external static pressure

E.S.P

 

 

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

207

(97)

@ 0.2" (50 Pa)

200

(94)

@ 0.3" (75 Pa)

184

(87)

@ 0.4" (100 Pa)

171

(80)

@ 0.5" (125 Pa)

152

(71)

@ 0.6" (150 Pa)

130

(61)

@ 0.7" (175 Pa)

116

(55)

@ 0.8" (200 Pa)

86

(40)

Max. Temperature Recovery

74%

 

 

 

Sensible Effectiveness

 

 

@ 66 cfm (31 L/s)

32°F (0°C)

74%

*Sensible Efficiency

 

 

@ 66 cfm (31 L/s)

32°F (0°C)

64%

*Sensible Efficiency

 

 

@ 109 cfm (51 L/s)

-13°F (-25°C)

62%

 

 

 

VAC @ 60HZ

 

120

 

 

 

WATTS / Low speed.

 

87

 

 

 

WATTS / High speed

 

164

Amp rating

 

1.4

*Sensible Efficiency – thermal **Latent Efficiency – moisture Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs

 

220

 

 

 

 

 

3 - High Speed

 

 

200

3

 

 

 

 

*2 - Medium Low Speed

 

 

 

 

 

 

*1 - Low speed

 

 

180

 

 

 

 

 

* Manufacturers Data

 

 

 

 

 

 

 

 

 

(cfm)

160

 

 

 

 

 

 

 

 

 

140

 

 

 

 

 

 

 

 

 

Flow

 

 

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

Air

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

80

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Static Pressure (in w.g.)

All units conform to CSA and UL standards

Dimensions RNC200

FRESH AIR

STALE AIR

FROM OUTSIDE

FROM INSIDE

 

inches (mm)

RECIRCULATING Dimensions RNC200 DEFROST Contractor: __________________________________________Supplier: ____________________________________________ DAMPER

FILTERS

*NOTE: Front clearance

CORE

BLOWERS

MOTOR

 

STALE AIR

FRESH AIR

TO OUTSIDE

TO INSIDE

 

 

33 5/8"

19" (483 mm)

CONDENSATE DRAINS

(850 mm) BALANCING DAMPER

of 25 inches (635 mm)

is recommended for servicing unit.

*All Duct Connections 6" (150 mm)

143/4"

(375 mm)

Date: _______________________________________________

Contractor: __________________________________________

Tag: __________________________Qty:__________________

Supplier: ____________________________________________

Project: _____________________________________________

Quote#: _____________________________________________

Engineer:____________________________________________

Submitted by: ________________________________________

6

SP-RNC200

 

Page 6
Image 6
Lifebreath RNC155 Engineering Data - HRV, Model RNC200, Dimensions RNC200, Date, Contractor, Tag Qty, Supplier, Project