Lifebreath RNC10 Defrost Operation, Recirculating Damper Defrost 4 port models, Factory Setting

Models: RNC155 RNC20 RNC95 RNC120D RNC10 RNC200 RNC5-TPD

1 36
Download 36 pages 54.76 Kb
Page 23
Image 23
Defrost Operation

Defrost Operation

Recirculating Damper Defrost (4 port models)

The recirculating damper defrost HRV has an electronically controlled damper defrost mechanism. The defrost timer is activated when the outside temperature drops below 27°F (- 3°C). A motor driven damper door mechanism closes off the supply air from outside allowing the exhaust air to recirculate through the unit. After the defrost period, the damper operates in the opposite direction to reopen the fresh air port. Defrost cycle repeats until the temperature again rises above 27°F (-3°C).

Damper Defrost (5 port models)

FRESH AIR

FROM OUTSIDE

RECIRCULATING Recirculating Damper Defrost (4 port models)Damper Defrost (5 port models) FILTERS DEFROST Defrost Cycle DIP Switch Settings - Increasing the Run TimeFactory SettingOption 1* DAMPER

CORE

STALE AIR

TO OUTSIDE

STALE AIR

FROM INSIDE

BLOWERS

MOTOR

FRESH AIR

TO INSIDE

The damper defrost HRV has a fifth port for defrost. An electronically controlled damper defrost mechanism activates the defrost timer when the outside temperature drops below 27°F (-3°C). A motor driven damper door mechanism closes off the supply air from outside allowing room air to enter through the fifth port of the unit. After the defrost period, the damper operates in the opposite direction to reopen the fresh air port. Defrost cycle repeats until the temperature again rises above 27°F (-3°C).

FRESH AIR

FROM OUTSIDE

DEFROST

DAMPER

DEFROST

PORT

FILTERS

STALE AIR

FROM INSIDE

STALE AIR

TO OUTSIDE

BLOWERS

FRESH AIR TO INSIDE

Defrost Cycle DIP Switch Settings - Increasing the Run Time

Defrost DIP Switch Settings (located on the circuit board) can be adjusted to increase the unit’s run (ventilation) time. The three minute defrost time cannot change.

3 minute defrost timeCAUTION

Lengthening the run time may result in ice buildup on the core.

Factory Setting

 

Option 1*

 

Option 2*

3 minute defrost time

3 minute defrost time

3 minute defrost time

17 minute run time

25 minute run time

30 minute run time

 

 

ON

 

 

ON

 

 

ON

 

 

 

 

HS

REMOTE

DFR2

DFR3

HS

REMOTE

DFR2

OFF DFR3

 

HS

 

REMOTE

 

DFR2

ON

DFR3

17 minute run time OFF

25 minute run time30 minute run time ON

SW1

SW1

SW1

*Lengthening the run time may result in ice build-up on the core.

23

Page 23
Image 23
Lifebreath RNC10 manual Defrost Operation, Recirculating Damper Defrost 4 port models, Damper Defrost 5 port models, Option