Image 9
Model RNC5-TPD

Engineering Data - HRV

Model RNC5-TPD

 

 

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE

The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.

MOTORS AND BLOWERS

Each air stream has an independent motorized impeller. 2 speed fan operation.

FILTERS

Washable air filters in exhaust and supply air streams.

DEFROST

Recirculating damper defrost system.

CASE

Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 1/2" (12 mm) OD.

MOUNTING THE HRV

Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.

DUCT CONNECTIONS

4 - 5” (127 mm) duct connections.

WEIGHT 61 lbs. (28 kg) SHIPPING WEIGHT 64 lbs. (29 kg)

CONTROLS- HRV System Control

HRV defaults to user selected speed from switch on top of cabinet when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV.

OFF(Standby)/LOW or OFF/HIGH speed operation is also available.

OPTIONAL MAIN CONTROLS (only one main control can be installed on the system)

99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.)

99-2040

20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch.

 

The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low

 

speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire

 

(min.) 100' length (max.)

99-RECIRC

Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch.

 

The Recirculation Switch will toggle from continuous low speed ventilation to

 

continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.)

99-130

Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100'

 

length (max.)

OPTIONAL TIMERS

99-132

20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20

 

gauge wire (min.) 100’ length

99-104

Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3

 

wire) 20 gauge wire (min.) 100' length

99-101

60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire)

 

20 gauge wire (min.) 100' length (max.)

WARRANTY

Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.

Performance (H.V.I. certified)

Net supply air flow in cfm (L/s) against external static pressure

E.S.P

 

 

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

169

(80)

@ 0.2" (50 Pa)

156

(73)

@ 0.3" (75 Pa)

149

(70)

@ 0.4" (100 Pa)

136

(64)

@ 0.5" (125 Pa)

126

(59)

@ 0.6" (150 Pa)

116

(54)

@ 0.7" (175 Pa)

103

(48)

@ 0.8" (200 Pa)

89

(42)

@ 0.9" (225 Pa)

77

(36)

@ 1.0" (250 Pa)

58

(27)

Max. Temperature Recovery

78%

 

 

 

Sensible Effectiveness

 

 

@ 66 cfm (31 L/s)

32°F (0°C)

74%

*Sensible Efficiency

 

 

@ 66 cfm (31 L/s)

32°F (0°C)

61%

*Sensible Efficiency

 

 

@ 76 cfm (36 L/s)

-13°F (-25°C)

63%

 

 

 

VAC @ 60HZ

 

120

 

 

 

WATTS / Low speed.

 

69

 

 

 

WATTS / High speed

 

147

 

 

 

Amp rating

 

1.7

*Sensible Efficiency - thermal **Latent Efficiency - moisture

Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency - takes into account all power inputs

 

180

 

 

 

 

 

 

 

3 - High Speed

 

 

 

 

3

 

 

 

 

 

 

 

 

 

160

 

 

 

 

 

 

*2 - Medium Low Speed

 

 

 

 

 

 

 

 

*1 - Low speed

 

 

 

140

 

 

 

 

 

 

 

* Manufacturers Data

 

 

 

 

 

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

(cfm)

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flow

80

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

1

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

Static Pressure (in w.g.)

All units conform to CSA and UL standards

Dimensions

 

 

RNC5-TPD

15”

 

inches (mm)

(378 mm)

 

 

 

 

27”

 

 

(690 mm)

 

 

2-1/4”

 

 

(57 mm)

SPEED

 

 

 

 

SELECTION

 

18-3/4”

SWITCH

 

(475 mm)

 

Date: _______________________________________________

Contractor: __________________________________________

Tag: __________________________Qty:__________________

Supplier: ____________________________________________

Project: _____________________________________________

Quote#: _____________________________________________

Engineer:____________________________________________

Submitted by: ________________________________________

9

SP-RNC5-TPD

Page 9
Image 9
Lifebreath RNC10 Engineering Data - HRV, Model RNC5-TPD, Dimensions, Performance H.V.I. certified, Date, Tag Qty, Project