Air Flow Balancing using the Door Ports | Models RNC155 and RNC200 Only |
|
|
The door ports ( MODELS RNC155 & RNC 200) are designed to quickly and measure the airflows for balancing.
Normally the HRV would be balanced on high speed. If the HRV is connected to a forced air system, both systems should be set to run at the highest operational speed when balancing is performed.
Balancing Procedure
Step 1 Remove balancing port covers.
Step 2 Insert one end of each connection hose into a rubber fitting. (Use light pressure until fitting is snug).
Step 3 Attach the connection hoses to pressure gauge
Step 4 Fresh Air - Connect hoses to door ports as illustrated (record reading).
Step 5 Stale Air - Connect hoses to door ports as illustrated (record reading).
Step 6 Refer to the Airflow Reference Chart for the conversion of gauge reading to airflow reading.
Step 7 Damper the airflows as required to balance the system.
The fresh airflow must equal the stale airflow. Step 8 Repeat steps 4 to 7 as required to confirm airflows.
Fresh Air
Step 4
Measuring Fresh Air Side (Connect to both ports at the same time).
MAGNEHELIC | Pressure |
| Gauge |
Stale Air
Step 5
Measuring Stale Air Side (Connect to both ports at the same time).
| Pressure |
MAGNEHELIC | Gauge |
Magnehelic Door Port Balancing Kit
Part No.
Use the Magnehelic Gauge Kit (Part No.
1 | - Pressure Gauge | 4 | - Rubber Fittings |
2 | - Connection Hoses | 1 | - Instruction Page |
Airflow Reference Chart
Pressure Gauge | Fresh Air | Stale Air |
Reading | Stream Flow | Stream Flow |
(in w.g.) | (cfm) | (cfm) |
0.070 | 75 | 54 |
0.080 | 80 | 59 |
0.090 | 84 | 65 |
0.100 | 89 | 70 |
0.110 | 93 | 75 |
0.120 | 98 | 81 |
0.130 | 102 | 86 |
0.140 | 106 | 91 |
0.150 | 111 | 97 |
0.160 | 115 | 102 |
0.170 | 120 | 114 |
0.180 | 124 | 118 |
0.190 | 128 | 123 |
0.200 | 133 | 128 |
0.210 | 137 | 133 |
0.220 | 142 | 138 |
0.230 | 146 | 143 |
0.240 | 151 | 148 |
0.250 | 155 | 153 |
0.260 | 159 | 158 |
0.270 | 164 | 163 |
0.280 | 168 | 167 |
0.290 | 173 | 172 |
0.300 | 177 | 177 |
0.310 | 181 | 182 |
0.320 | 186 | 187 |
0.330 | 190 | 192 |
0.340 | 195 | 197 |
Door port balancing is only available for Models RNC155 and RNC200.