2 Speed RNC Electronics
RNC Series
Models
Leave this Manual for the Homeowner
IMPORTANT
Please read this manual before installing the HRV (Heat Recovery Ventilator).
NOTE
RNC95
Engineering Data - HRV Model RNC95
Round port bent to oval
Engineering Data - HRV Model RNC155
RNC155
RNC200
Engineering Data - HRV Model RNC200
Engineering Data - HRV Model RNC10
RNC10
Engineering Data - HRV Model RNC20
RNC20
Engineering Data - HRV Model RNC5-TPD
Performance
RNC5-TPD
Engineering Data - HRV Model RNC120D
RNC120D
Engineering Data - HRV Model RNC120D
Connect drain hose to spout located in door.
Option 1 - Horizontal Duct Configuration Dimensions
Connect drain hose to the two field installed spouts located on the bottom of the unit.
Option2-Vertical Duct Configuration Dimensions inches
Ventilation Dehumidistat
20/40 ON/OFF Dehumidistat
Recirculation Control
Remote Dehumidistat
20 Minute Timer
Page
The unit must be mounted level for proper drainage of the condensate pans.
ATTENTION
Page
Page
The Simplified Installation (Return/Return Method)
FIVE PORT MODELS - Simplified Installation for Models RNC10/RNC20
It is mandatory that the furnace run continuously or HRV
Check local codes/authority having jurisdiction for
NOTES:
The Partially Dedicated Installation
FIVE PORT MODELS - Partially Dedicated Installation for Models RNC10/RNC20
Stale air drawn from key areas of home
Fresh air supplied to return air duct of air handler HRV must be balanced.
FOUR PORT MODELS
The Fully Dedicated Installation
FIVE PORT MODELS - Fully Dedicated Installation for Models RNC10/RNC20
Stale air drawn from key areas of home
Fresh air supplied to main living areas of house HRV must be balanced.
FOUR PORT MODELS - Models RNC155/RNC200
Intake Weatherhood Requirements
Exhaust Weatherhood Requirements
Local codes may require greater distances.
Grilles
Grilles and Weatherhoods
ATTENTION
Dehumidistat Ventilation Control
Part No. 99-116
Part No. 99-RECIRC
Part No. 99-101
ATTENTION
Wiring the Controls
Page
Prior to balancing, ensure that:
Air Flow Balancing
Balancing Procedure
DUCT DIAM. (inches) CROSSSECTION AREA (sq. ft.)
5 0.14 6 0.20 7 0.27
Air Flow Balancing
Placement of Pitot Tube HRV
1/2
ATTENTION
Apply use of balancing dampers as required.
NOTE
Graphic is for illustrative purposes only. Duct connection ports may vary.
Step 5
Fresh Air
Stale Air
Step 6
Fresh Air
Step 4
Airflow Reference Chart
Stale Air
Step 5
Page
Wiring Diagrams Model RNC5-TPD
BLUE
DEFROST DETAILS
Model RNC5 (Only)
PCB PLUG - IN
Wiring Diagrams RNC120D HRV Control Box
DEFROST DETAILS
60-120D-WIRING
PCB PLUG - IN
BI-DIRECTIONAL DAMPER MOTOR
RNC3WIRINGDIAGRAM
HIGHVOLTAGE 12VLOWVOLTAGE FIELDINSTALLED
12VLOWVOLTAGE
FANMOTORDETAILS
DEFROSTDETAILS
Troubleshooting
Symptom Cause Solution
Poor Air Flow
Supply air feels cold
1. Inspect Exterior Hoods at least once a month.
Maintenance HRV
2. Clean Air Filters - Twice a Year
3. Clean Core - Twice a Year
To install the clean core: