SECTION 6: ROUTINE MAINTENANCE

SECTION 6: ROUTINE MAINTENANCE

GENERAL

1 Routine maintenance should be carried out on a six monthly and annual basis as detailed below.

SIX MONTHLY CHECK

2The following must be carried out every six months:

2.1Check that the unit output voltage is within the normal operating limits of the external power system (refer to the power system manufacturer's handbook).

Note

Voltages outside the normal operating range may be attributed to a recent interruption of the dc supply.

2.2Check that the LVD PCA LED is lit.

2.3Make a visual inspection for mechanical damage, signs of overheating and damaged cables, terminals and insulation.

2.4Check that all electrical connections and mechanical fixings are secure.

3Record any faults in the service log.

ANNUAL CHECK

4As well as the six monthly checks listed in Para 2, it is recommended that a battery discharge test is carried out on a battery connected to the unit output. For details, refer to the battery manufacturer's documentation.

Text artwork 990-9030 Rev. A. Equipment Handbook for the Low Voltage Disconnectors series