8.0Storing the UPS
8.1Storage Conditions
The UPS should be covered and stored in a cool dry location. The UPS should be stored with the Battery Packs in a fully charged state. That is, the reported battery capacity should be at 100% before the UPS is switched off for storage. Disconnect the Battery Packs from the UPS and from each other (where applicable). Store the Battery Packs in an upright position.
8.2 Extended Storage
To achieve expected run time following extended storage, the UPS should be allowed to refresh the Battery Packs every 6 months in environments where the ambient temperature is
9.0 Specifications
Note: Where specification ratings differ, values for the UPS configured for 240 Vac operation are given in brackets [ ].
9.1 Input
Nominal input voltage: single phase 208 Vac [240 Vac].
Nominal input frequency: 60 Hz.
Input circuit breaker: 20 Amp, 30 Amp; for the 3000VA and 5000VA models, respectively.
Input connector: NEMA
9.2 Transfer Characteristics
Frequency limits for
Input voltage limits for
Transfer to/from
Transfer to/from bypass: Transfers to and from bypass occur synchronously with the utility voltage phase. Transfers both to and from bypass mode occur in 0 mS typically.
9.3 Output Characteristics
Maximum load: 3000 VA or 2250 W @ 0.75 power factor; 4700 VA or 3750 W @ 0.8 power factor [5000 VA, 3750 W @ 0.75 power factor] for the 3000VA and 5000VA models, respectively.
Nominal output voltages: 208 Vac / 120 Vac [240 Vac / 120 Vac].